4.3  Dielectric Strength (HIPOT) Testing 
 
For dielectric strength (HIPOT) testing in the field, users must remove the metal jumper located on 
terminal 2, 4, and 6 of the power supply terminal block.  This metal jumper connects transient 
suppression circuitry to chassis ground and must be removed in order to avoid damage to transient 
suppression circuitry during HIPOT testing.  Figure 11 shows the proper HIPOT test connections 
and should be followed to avoid damage to the device.   
 
 
Figure 11: Dielectric Strength (HIPOT) Testing