Rheem RJNA Series 用户手册

下载
页码 50
COOLING PERFORMANCE DATA—RJNA-A036
HEATING PERFORMANCE DATA—RJNA-A036
DR —Depression ratio
dbE —Entering air dry bulb
wbE—Entering air wet bulb
Total —Total capacity x 1000 BTUH
Sens —Sensible capacity x 1000 BTUH
Power—KW input
NOTES:
➀ When the entering air dry bulb is other than 80°F [27°C], adjust the sensible
capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].
IDB—Indoor air dry bulb
[
] Designates Metric Conversions
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE 
wbE
71°F [21.7°C]
67°F [19.4°C]
63°F [17.2°C]
CFM [L/s]
1440 [680]
1200 [566]
960 [453]
1440 [680]
1200 [566]
960 [453]
1440 [680]
1200 [566]
960 [453]
DR
.16
.13
.08
.16
.13
.08
.16
.13
.08
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]
75
[23.9]
Total BTUH [kW]
Sens BTUH [kW]
Power
46.4 [13.60]
27.9 [8.18]
2.2
44.8 [13.13]
25.5 [7.47]
2.2
43.1 [12.63]
23.1 [6.77]
2.2
43.4 [12.72]
33.5 [9.82]
2.2
41.9 [12.28]
30.6 [8.97]
2.2
40.4 [11.84]
27.7 [8.12]
2.1
41.1 [12.05]
34.8 [10.20]
2.2
39.7 [11.63]
31.8 [9.32]
2.2
38.2 [11.20]
28.8 [8.44]
2.1
80
[26.7]
Total BTUH [kW]
Sens BTUH [kW]
Power
45.5 [13.33]
27.3 [8.00]
2.3
43.9 [12.87]
25.0 [7.33]
2.3
42.3 [12.40]
22.6 [6.62]
2.3
42.6 [12.48]
32.9 [9.64]
2.3
41.1 [12.05]
30.0 [8.79]
2.3
39.6 [11.61]
27.2 [7.97]
2.3
40.2 [11.78]
34.2 [10.02]
2.3
38.8 [11.37]
31.3 [9.17]
2.3
37.4 [10.96]
28.3 [8.29]
2.3
85
[29.4]
Total BTUH [kW]
Sens BTUH [kW]
Power
44.5 [13.04]
26.7 [7.83]
2.5
42.9 [12.57]
24.4 [7.15]
2.4
41.3 [12.10]
22.1 [6.48]
2.4
41.5 [12.16]
32.3 [9.47]
2.4
40.0 [11.72]
29.5 [8.65]
2.4
38.6 [11.31]
26.8 [7.85]
2.4
39.2 [11.49]
33.6 [9.85]
2.4
37.8 [11.08]
30.7 [9.00]
2.4
36.4 [10.67]
27.9 [8.18]
2.4
90
[32.2]
Total BTUH [kW]
Sens BTUH [kW]
Power
43.3 [12.69]
26.1 [7.65]
2.6
41.7 [12.22]
23.9 [7.00]
2.5
40.2 [11.78]
21.7 [6.36]
2.5
40.3 [11.81]
31.7 [9.29]
2.6
38.9 [11.40]
29.0 [8.50]
2.5
37.5 [10.99]
26.3 [7.71]
2.5
38.0 [11.14]
33.0 [9.67]
2.6
36.6 [10.73]
30.2 [8.85]
2.5
35.3 [10.35]
27.4 [8.03]
2.5
95
[35]
Total BTUH [kW]
Sens BTUH [kW]
Power
42.0 [12.31]
25.6 [7.50]
2.7
40.5 [11.87]
23.4 [6.86]
2.6
39.0 [11.43]
21.2 [6.21]
2.6
39.0 [11.43]
31.1 [9.11]
2.7
37.6 [11.02]
28.5 [8.35]
2.6
36.3 [10.64]
25.8 [7.56]
2.6
36.7 [10.76]
32.4 [9.50]
2.7
35.4 [10.37]
29.7 [8.70]
2.6
34.1 [9.99]
26.9 [7.88]
2.6
100
[37.8]
Total BTUH [kW]
Sens BTUH [kW]
Power
40.7 [11.93]
25.0 [7.33]
2.8
39.3 [11.52]
22.8 [6.68]
2.8
37.8 [11.08]
20.7 [6.07]
2.7
37.7 [11.05]
30.5 [8.94]
2.8
36.4 [10.67]
27.9 [8.18]
2.7
35.1 [10.29]
25.3 [7.41]
2.7
35.4 [10.37]
31.9 [9.35]
2.8
34.2 [10.02]
29.1 [8.53]
2.7
32.9 [9.64]
26.4 [7.74]
2.7
105
[40.6]
Total BTUH [kW]
Sens BTUH [kW]
Power
39.5 [11.58]
24.4 [7.15]
2.9
38.1 [11.17]
22.3 [6.54]
2.9
36.7 [10.76]
20.2 [5.92]
2.8
36.5 [10.70]
30.0 [8.79]
2.9
35.2 [10.32]
27.4 [8.03]
2.9
33.9 [9.94]
24.8 [7.27]
2.8
34.2 [10.02]
31.3 [9.17]
2.9
33.0 [9.67]
28.6 [8.38]
2.9
31.8 [9.32]
25.9 [7.59]
2.8
110
[43.3]
Total BTUH [kW]
Sens BTUH [kW]
Power
38.4 [11.25]
23.8 [6.98]
3.0
37.0 [10.84]
21.8 [6.39]
3.0
35.7 [10.46]
19.7 [5.77]
2.9
35.4 [10.37]
29.3 [8.59]
3.0
34.2 [10.02]
26.8 [7.85]
3.0
32.9 [9.64]
24.3 [7.12]
2.9
33.1 [9.70]
30.7 [9.00]
3.0
31.9 [9.35]
28.0 [8.21]
3.0
30.8 [9.03]
25.4 [7.44]
2.9
115
[46.1]
Total BTUH [kW]
Sens BTUH [kW]
Power
37.5 [10.99]
23.2 [6.80]
3.1
36.1 [10.58]
21.2 [6.21]
3.1
34.8 [10.20]
19.2 [5.63]
3.0
34.5 [10.11]
28.7 [8.41]
3.1
33.3 [9.76]
26.3 [7.71]
3.1
32.1 [9.41]
23.8 [6.98]
3.0
32.2 [9.44]
30.0 [8.79]
3.1
31.0 [9.09]
27.5 [8.06]
3.1
29.9 [8.76]
24.9 [7.30]
3.0
45
[46.1]
Total BTUH [kW]
Power
35.4 [10.37]
2.4
34.9 [10.23]
2.5
34.4 [10.08]
2.6
33.6 [9.85]
2.7
33.1 [9.70]
2.7
32.6 [9.55]
2.8
31.9 [9.35]
2.9
IDB
31.4 [9.20]
3.0
31.0 [9.09]
3.1
60°F [15.5°C]
50
[10]
70°F [21.1°C]
Total BTUH [kW]
Power
37.6 [11.02]
2.5
80°F [26.7°C]
37.1 [10.87]
2.5
36.6 [10.73]
2.6
CFM [L/s]
35.8 [10.49]
2.7
35.3 [10.35]
2.8
1440 [680]
1200 [566]
960 [453]
1440 [680]
1200 [566]
960 [453]
1440 [680]
1200 [566]
960 [453]
34.8 [10.20]
2.8
34.1 [9.99]
2.9
33.6 [9.85]
3.0
33.1 [9.70]
3.1
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]
0
[-17.8]
Total BTUH [kW]
Power
8.9 [2.61]
2.1
8.7 [2.55]
2.1
8.6 [2.52]
2.2
7.0 [2.05]
2.3
6.9 [2.02]
2.4
6.8 [1.99]
2.4
5.3 [1.55]
2.6
5.2 [1.52]
2.6
5.1 [1.49]
2.7
5
[26.7]
Total BTUH [kW]
Power
12.2 [3.58]
2.1
12.0 [3.52]
2.2
11.9 [3.49]
2.2
10.4 [3.05]
2.4
10.2 [2.99]
2.4
10.1 [2.96]
2.5
8.6 [2.52]
2.6
8.5 [2.49]
2.7
8.4 [2.46]
2.7
10
[-12.2]
Total BTUH [kW]
Power
15.5 [4.54]
2.2
15.3 [4.48]
2.2
15.1 [4.43]
2.3
13.6 [3.99]
2.4
13.5 [3.96]
2.5
13.3 [3.90]
2.5
11.9 [3.49]
2.6
11.8 [3.46]
2.7
11.6 [3.40]
2.8
15
[32.2]
Total BTUH [kW]
Power
18.7 [5.48]
2.2
18.5 [5.42]
2.3
18.2 [5.33]
2.3
16.9 [4.95]
2.4
16.6 [4.86]
2.5
16.4 [4.81]
2.6
15.1 [4.43]
2.7
14.9 [4.37]
2.8
14.7 [4.31]
2.8
20
[-6.6]
Total BTUH [kW]
Power
21.8 [6.39]
2.2
21.5 [6.30]
2.3
21.2 [6.21]
2.4
20.0 [5.86]
2.5
19.7 [5.77]
2.5
19.4 [5.69]
2.6
18.3 [5.36]
2.7
18.0 [5.28]
2.8
17.7 [5.19]
2.9
25
[37.8]
Total BTUH [kW]
Power
24.8 [7.27]
2.3
24.5 [7.18]
2.3
24.1 [7.06]
2.4
23.0 [6.74]
2.5
22.7 [6.65]
2.6
22.3 [6.54]
2.6
21.3 [6.24]
2.8
21.0 [6.15]
2.8
20.7 [6.07]
2.9
30
[-1.1]
Total BTUH [kW]
Power
27.7 [8.12]
2.3
27.3 [8.00]
2.4
26.9 [7.88]
2.4
25.9 [7.59]
2.5
25.5 [7.47]
2.6
25.1 [7.36]
2.7
24.1 [7.06]
2.8
23.8 [6.98]
2.9
23.5 [6.89]
2.9
35
[43.3]
Total BTUH [kW]
Power
30.5 [8.94]
2.4
30.0 [8.79]
2.4
29.6 [8.67]
2.5
28.6 [8.38]
2.6
28.2 [8.26]
2.6
27.8 [8.15]
2.7
26.9 [7.88]
2.8
26.5 [7.77]
2.9
26.1 [7.65]
3.0
40
[4.4]
Total BTUH [kW]
Power
33.0 [9.67]
2.4
32.6 [9.55]
2.5
32.1 [9.41]
2.5
31.2 [9.14]
2.6
30.7 [9.00]
2.7
30.3 [8.88]
2.7
29.5 [8.65]
2.9
29.0 [8.50]
2.9
28.6 [8.38]
3.0
15
SYSTEMS PERFORMANCE—RJNA- SERIES