D-2 
 
Review the guidelines below before initiating an Earth Fault Search. 
•  The Detect Earth Fault jumper must be installed at the SPS for earth fault detection to 
occur. 
•  Only one power supply per location is configured to detect earth faults. 
•  For more reliable earth fault searching: 
Use IDNet channel isolators to isolate channel faults to a specific 
segment of channel wiring. 
Set IDNet channel isolator addresses to the lowest IDNet device 
addresses, increasing with communication distance from the IDNet 
card. 
•  If an earth fault is suspected on the IDNet channel with multiple isolators, start 
an IDNet Channel Search before doing a Location Search. If the Location Search 
is done first, it may not yield the correct location (this is a by-product of the 
extended amount of time required for the IDNet channel to initialize during a 
Location Search).  
•  Earth Fault Search detects only one fault at a time. Multiple faults require fixing 
the first fault and then repeating the search. 
•  The 4100U-S1 suspends normal operation for the duration of the Earth Fault 
Search. 
•  Location Earth Fault Searches optionally allow exclusion of auxiliary power 
circuits from the search, so that modules connected to the 24 V auxiliary outputs 
can remain in operation during the search. 
•  The option to exclude auxiliary power circuits does not apply to IDNet devices, 
because the entire IDNet communication channel is isolated during each search. 
•  During the search, all related troubles are suppressed and a single trouble 
pseudo-point is activated (P438). 
•  At the completion of the search, all slaves are restarted and normal panel 
operation resumes. 
•  Earth Fault Search is only supported by new 4100U modules. 4100 Legacy (slot 
format) modules are not supported, with the following exceptions: 
IPS for earth fault detection (not recommended). The Earth Fault 
Search may fail because the isolation circuits of some 4100U slaves 
(such as the 4100U telephone slave) do not support IPS. 
 
IMPORTANT: The fire panel cannot provide fire protection during an Earth 
Fault Search. 
 
General Guidelines