  MACH®  Series
 
Gas-Fired Boiler 
Installation 
 
 
Page  23 
 
CAUTION!  
Terminal 10 and 11 on TB2 are for pilot duty only.  
they should not be connected directly to the 
pump. 
Outdoor Air Reset (optional): 
OU TD OO R   A IR   vs  B OI LER  SETP O IN T
70
80
90
100
110
120
130
140
150
160
170
180
190
0
10
20
3 0
40
50
60
70
8 0
9 0
OUTDOO R AIR TE MP  °F
B
O
IL
ER
 SET
PO
IN
T
 °
F
 
 
The control automatically detects the presence of the 
outdoor air sensor.  If an outdoor air sensor is present, 
the boiler automatically defaults to outdoor air reset 
for setting boiler temp.  The parameters should be set 
according to the following table: 
 
Item Parameter 
Value 
°F 
Allowable 
Range °F 
Maximum Setpoint 
180 
68-185 
Minimum Setpoint 
80 
60-140 
Outdoor Air 
Minimum Temp.  
6 20 
4-50 
Outdoor Air 
Maximum Temp.  
7 70 
59-77 
Boiler Shutoff Temp. 
10 
90 
32-140 
(32=off) 
Outdoor Air Offset 
12 
0-144 
Boiler Configuration 
34 
01 
 
 
 
The set point of the boiler is controlled by an outdoor 
temperature sensor.  As the outdoor temperature falls 
the setpoint of the boiler is increased.  The boiler 
modulates to maintain this setpoint. 
The setpoint is adjusted according to the above 
parameters.  The boiler setpoint will be the maximum 
value (180° F) when the outdoor air is at or below a 
minimum temperature value (20° F).  The boiler 
setpoint will be at the minimum value (80° F), when 
outdoor air is at or above a maximum temperature 
value (70° F).  The setpoint for “in between“ values 
of outdoor air temperature, is linearly proportional to 
the above settings.  Using the values in the table 
above, the boiler setpoint will be 80° F when the 
outdoor air temperature is 70° F.  As the outdoor air 
temperature drops, the boiler setpoint will be 
increased until the outdoor air temperature is 20° F.  
At this point the boiler will reach its maximum 
setpoint of 180° F.  If the outdoor air temp drops 
further, the boiler setpoint remains at 180° F. 
The boiler shutoff temperature can be used to turn the 
boiler off at a given setpoint.  For example if you 
wanted to shut the boiler off when the outdoor air 
temperature was above 65° F you would set the boiler 
shutoff temp to 90° F since this is the setpoint that is 
called for at 65° F outside air temp.