Trane Gas Unit Heaters 维护手册

下载
页码 53
Installation: Piping
GTND-SVX01B-EN
27 
Unit sizes 30–120: Use 4” (120 mm) flue pipe.
Unit sizes 150–400: Refer to 
All heaters must be vented with a single or double wall 
pipe listed for Category III positive pressure vent 
systems. 
Unit sizes 30–120: Double wall pipe can be used with 
limitations as shown in Figure X. As illustrated, a single 
5 foot (1.52 m) section of double wall vent pipe with a 
draft hood connector may be used between the 
appliance vent connection and the vent terminal.
2. Each unit must have an individual vent pipe and 
vent terminal! Unit MUST NOT be connected to other 
vent systems or to a chimney.
3. The maximum equivalent length of vent pipe must not 
be exceeded:
Unit sizes 30–120: Category III units are limited to a 
maximum of 40 feet (12.19 m) equivalent length of 
vent pipe; equivalent length is the total length of 
straight sections PLUS 5 feet (1.5 m) for each 90° 
elbow and 2.5 feet (0.75 m) for each 45° elbow.
Unit sizes 150–400: The vent pipe equivalent length 
must not exceed 50  feet (15.2 m); equivalent length 
is the total length of straight sections PLUS 15 feet 
(4.6 m) for each 90° elbow and 8 feet (2.44 m) for 
each 45° elbow.
4. Seal all vent pipe joins and seams to prevent leakage. 
Use General Electric RTV-108, Dow-Corning RTV-732, 
or equivalent silicone sealant with a temperature 
rating of 500°F (see 
). Attach the draft 
hood connector to the appliance vent connection with 
screws (3 minimum) and seal the joint with silicone 
sealant. Install a vent thimble in the wall. Insert the vent 
pipe through the thimble and attach it to the adapter on 
the appliance. Seal the joint with silicone sealant or 
two wraps of aluminum foil tape. Install a vent cap on 
the outlet pipe and secure with screws (3 minimum).
Unit sizes 30–120: If using a single section of double 
wall vent pipe, seal the annular space between the 
inner and outer sections of the draft hood connector 
with a high temperature silicone sealant.
5. A vent cap must be supplied by the customer for each 
power vented unit:
Unit sizes 30–120: Use an Amerivent Americap or 
Metalbestos vent cap. The vent pipe diameter must be 
4”.
Unit sizes 150–400: Use a Breidert Type L, Fields 
Starkap, or equivalent vent cap. The the vent pipe 
diameter must be as specified in 
unit sizes are factory equipped with the required flue 
size collar; attach in place (if not mounted to outlet); 
refer to included vent collar instruction sheet for 
additional requirements.
6. Through the wall venting for these appliances shall not 
terminate over public walkways, or over an area where 
the condensate or vapor could create a nuisance, 
hazard, or could be detrimental to the operation of 
regulators, relief valves, or other equipment:
Unit sizes 30–120: Refer to 
Unit sizes 150–400: Refer to 
.
All unit sizes: Refer to 
 an
.
7.
The venting system for these appliances shall 
terminate at least 4 feet (1.2 m) below, 4 feet (1.2 m) 
horizontal from, or 1 foot (0.3 m) above any door, 
window, or gravity vent air inlet into the building.
8. Vent terminal:
Unit sizes 30–120: The vent terminal must be installed 
with a minimum horizontal clearance of 4 feet (1.2 m) 
from electrical meters, gas meters, regulators, and 
relief equipment.
Unit sizes 150–400: The vent terminal must be at least 
3 feet (1 m) above grade, or in snow areas, at least 
3 feet above the snow line to prevent blockage by 
snow.
9. The vent terminal must be at least 12 inches (305 mm) 
from the exterior of the wall that it passes through to 
prevent degradation of the building materials by flue 
gasses.
10. Unit sizes 150–400: The vent terminal must be installed 
with a minimum horizontal clearance of 4 feet (1.2 m) 
from electric meters, gas meters, regulators, and relief 
equipment.
11. Maintain clearance between the vent pipe and 
combustible materials according to vent pipe 
manufacturer’s instructions.
12. Seal all vent pipe joints and seams to prevent leakage. 
Use General Electric RTV-108, Dow-Corning RTV-732, 
or equivalent silicone sealant with a temperature 
rating of 500°F, or 3M #425 aluminum foil tape (or 
equivalent). The vent system must be installed to 
prevent collection of condensate. Pitch horizontal 
pipes downward 1/4 inch per foot (21 mm per meter) 
toward the outlet for condensate drainage.
Unit sizes 30–120: Install a tee with a condensate drain 
at the low point of the pipe (see 
). As an 
alternate, a 3/8 inch diameter hole may be drilled at the 
low point of the pipe for condensate drainage. 
13. Horizontal portions of the venting system shall be 
supported at minimum intervals of 4 feet (1.2 m) to 
prevent sagging (in Canada, support at 3 foot (1 m) 
minimum intervals).
14. Insulate pipe where appropriate:
Unit sizes 30–120: Avoid running vent pipe through 
unheated spaces; when this cannot be avoided, 
insulate the pipe to prevent condensation of 
moisture on the walls of the pipe. Insulate vent pipe 
runs longer than 10 feet (3 m). Insulation should be 
a minimum of 1/2 inch (12.7 mm) thick foil-faced.