Installation: Piping
30
 GTND-SVX01B-EN
Figure 28.
All unit sizes: Horizontal arrangement, single wall vent system to single wall termination
Vent pipe diameter
Unit sizes 30–120: See 
Unit sizes 150–400: See 
12” min.
(305 mm min.)
To prevent 
building material 
degradation from 
flue gases.
Pitch flue pipe down toward 
outlet 1/4” per foot 
(21 mm/m) of run to allow 
for condensate drainage
Unit sizes 30–120: 3 feet (0.91 m) 
plus maximum snow depth for 
area above grade
Unit sizes 150–400: 12 inches 
(305 mm) plus maximum snow 
depth for area above grade
3’-0” min.
(0.9 m min.)
6’-0” min.
(1.8 m min.)
Adjacent 
building
Building 
overhang
Approved 
vent cap 
(see instructions)
Flashing
Fiberglass 
insulation 
min. 2” thick 
(51 mm min.)
Flue 
dia.
2” min.
(51 mm min.)
all around
2” clearance 
(51 mm) 
thimble
Wall
Figure 29.
All unit sizes: Vertical arrangement, single wall vent system to single wall termination
Unit sizes 30–120: 2 feet (0.609 m) 
plus maximum snow depth for area
Unit sizes 150–400: 6 inches (152 mm) 
plus maximum snow depth for area
All unit sizes: Vertical pipe extension 
over 12” (305 mm) must be insulated
6’-0” min.
(1.8 m min.)
Adjacent building
Roof pitched 
from 0° to 45°
Approved 
vent cap 
(see instructions)
Roof
Flashing
Fiberglass 
insulation 
min. 2” thick 
(51 mm min.)
Flue 
dia.
2” min.
(51 mm min.)
all around
2” clearance 
(51 mm) 
thimble
Vent pipe diameter
Unit sizes 30–120: See 
Unit sizes 150–400: Se