Trane Gas Unit Heaters 维护手册
Installation: Piping
30
GTND-SVX01B-EN
Figure 28.
All unit sizes: Horizontal arrangement, single wall vent system to single wall termination
Vent pipe diameter
Unit sizes 30–120: See
Unit sizes 150–400: See
12” min.
(305 mm min.)
To prevent
building material
degradation from
flue gases.
Pitch flue pipe down toward
outlet 1/4” per foot
(21 mm/m) of run to allow
for condensate drainage
Unit sizes 30–120: 3 feet (0.91 m)
plus maximum snow depth for
area above grade
Unit sizes 150–400: 12 inches
(305 mm) plus maximum snow
depth for area above grade
3’-0” min.
(0.9 m min.)
6’-0” min.
(1.8 m min.)
Adjacent
building
Building
overhang
Approved
vent cap
(see instructions)
Flashing
Fiberglass
insulation
min. 2” thick
(51 mm min.)
Flue
dia.
2” min.
(51 mm min.)
all around
2” clearance
(51 mm)
thimble
Wall
Figure 29.
All unit sizes: Vertical arrangement, single wall vent system to single wall termination
Unit sizes 30–120: 2 feet (0.609 m)
plus maximum snow depth for area
Unit sizes 150–400: 6 inches (152 mm)
plus maximum snow depth for area
All unit sizes: Vertical pipe extension
over 12” (305 mm) must be insulated
6’-0” min.
(1.8 m min.)
Adjacent building
Roof pitched
from 0° to 45°
Approved
vent cap
(see instructions)
Roof
Flashing
Fiberglass
insulation
min. 2” thick
(51 mm min.)
Flue
dia.
2” min.
(51 mm min.)
all around
2” clearance
(51 mm)
thimble
Vent pipe diameter
Unit sizes 30–120: See
Unit sizes 150–400: See