Toshiba VF010H05 用户手册

下载
页码 106
JKSSS+ Series - 9
JKSSS+ Series   
 
 
 
 
           
            
   2.3 - 4.2KV
· 
Coast-To-Stop Mode: Power is immediately removed from the motor and the 
soft starter returns to the Ready Mode.
Additional protection features activated when the stop command is given include:
·  Coast-Down / Back Spin Timer 
·  Starts-per-Hour 
·  Time Between Starts
·  External Input Faults
1.7 Thermal Overload Protection
The JKSSS+ Series plays an important role in the protection of your motor in that it 
monitors the motor for excessive thermal conditions due to starting, running or even 
ambient conditions. The soft starter has a Dynamic Thermal Register system in the 
CPU that provides a mathematical representation of the thermal state of the motor. 
This thermal state information is kept in memory and is monitored for excesses in 
both value and rate of change. Input is derived from current  imbalances and RTD 
measurements making it dynamic to all processes involving the motor. The starter 
monitors these conditions separately during Start and Run modes to provide proper 
thermal overload protection at all times. 
Start Mode overload protection is selectable using one of three methods:
· 
Basic Protection: I
2
t data is accumulated and plotted based on an Overload 
Curve selected in programming. This is programmed per NEMA Class 5-30 
standard curves and is based on the Locked Rotor Current (from the motor 
nameplate) as programmed into the soft starter.
· 
Measured Start Capacity: The user enters a measured amount of thermal 
capacity from a pre-selected successful start as a setpoint to the Thermal Reg-
ister for the soft starter to follow.
· 
Learned Curve Protection: The user sets the soft starter to the “LEARN” 
mode and starts the motor under normal starting conditions. The CPU then 
samples and records 100 data points during the start curve, analyzes them and 
creates a graphical representation in memory. The soft starter is then switched 
to Curve Follow protection mode and monitors motor performance against this 
curve. This feature is especially useful in initial commissioning tests to record a 
base line performance sample (in this case, it is not necessarily used for motor 
protection).  
     
Run Mode overload protection is initiated when the starter determines that the 
motor is At-Speed. Overload Protection is initiated when the motor RMS current 
rises above a “pick-up point” (as determined by the motor nameplate FLA and 
service factor). Run mode protection is provided by the CPU monitoring the Dy-
namic Thermal Register. Data for the Dynamic Thermal Register is accumulated 
from I
2
t calculations and cooling rates. A trip occurs when the register reaches 
100% as determined by the selected Overload Protection Curve (NEMA Class 
5-30 standard curves) and is based on the programmed Locked Rotor Current 
indicated on the motor nameplate. The Dynamic Thermal Register is altered, or 
“biased”, by the following conditions:
· 
Current Imbalance: Will bias the register higher to add protection from ad-
ditional motor heating during a current imbalance condition.
· 
Normal Cooling: Provided when the motor current drops below the pick-up 
point or the motor is off line. The cooling rate is lower for
 motors that are off-line 
(such as after a trip) since cooling fans are also inoperative