Thomas & Betts 9395 用户手册

下载
页码 74
 
 
UPS 225 - 275 kVA  
User’s and Installation Guide
1027212 
Revision B
70
8 UPS maintenance
The components inside the UPS cabinet are secured to a sturdy metal frame. All repairable 
parts and assemblies are located for easy removal, with very little disassembly. This design 
allows authorized service personnel to perform routine maintenance and servicing quickly. 
You must schedule periodic performance checks of your UPS system to keep it running 
properly. Regular routine checks of operation and system parameters enable your system to 
function efficiently for many trouble-free years.
8.1 Important safety instructions
Remember that your UPS system is designed to supply power EVEN WHEN DISCONNECTED 
FROM THE UTILITY POWER. The UPS module interiors are unsafe until the DC power source 
is disconnected and the electrolytic capacitors are discharged. After disconnecting the utility 
power and the DC power, authorized service personnel should wait at least five minutes for 
capacitor bleedoff before attempting internal access to the UPS module.
WARNING
•  Servicing and maintenance should be performed by qualified service personnel only.

•  LETHAL VOLTAGE PRESENT. This unit should not be operated with the cabinet doors
 open or protective panels removed. Do not make any assumptions about the electrical
 state of any cabinet in the UPS system.
Since each battery string is an energy source in itself, opening the battery circuit breaker does 
not de-energize the voltage within the battery string. DO NOT ATTEMPT TO ACCESS ANY 
INTERNAL AREA OF THE BATTERY STRING YOURSELF. VOLTAGES ARE ALWAYS PRESENT IN 
THE BATTERY STRING. If you suspect that a battery string needs service, you should contact 
your service representative.
If the string requires service, refer to the battery manufacturer’s operating manual for 
instructions on battery maintenance or contact your service representative. 
Observe these precautions when working on or around batteries:
Remove watches, rings, or other metal objects.
Use tools with insulated handles.
Wear rubber gloves and boots.
Do not lay tools or metal parts on top of batteries or battery cabinets.
Disconnect the charging source prior to connecting or disconnecting terminals.
Determine if the battery is inadvertently grounded. If it is, remove the source of the ground. 
Contact with any part of a grounded battery can result in electrical shock. The likelihood of 
such shock is reduced if such grounds are removed during installation and maintenance.
When replacing batteries, use the same number of sealed, lead-acid batteries.
Proper disposal of batteries is required. Refer to your local codes for disposal requirements.