3. Select the item to be changed. The window corresponding to the item to be
changed will be displayed.
Destination PC
Communications Port
Baud Rate
Unit No.
Parity
Data Bits
Stop Bits
If the Controller Link Support Software is to be connected to a CVM1 or CV-
series PC, set a baud rate of at least 4,800 bps, and if it is to be connected to
a CS1-series PC, set a baud rate of at least 9,600 bps.
4. Select the desired setting from the window. In the Unit No. Window, use Nu-
meric Keys to enter a number between 00 and 31, then press the Enter Key.
In windows other than the Unit No. Window, select one of the settings.
5. If a C-series PC is selected as the destination PC, the following window will
be displayed to prompt you to select the operating level of the Controller Link
Unit to be used.
If a CQM1H is selected as the PC, be sure to select operation level 0.
6. If another item is also to be set, press the Escape Key to return to the pre-
vious screen.
5-14-4 Setting the Node Response Time — T: Watchdog Timer
If an error occurs during communications between the Controller Link Support
Software and a node, the node may not be able to send a response to a request
sent by the Controller Link Support Software. “T: Watchdog timer” is used to set
the maximum node response time to be monitored. Failure to send a response
within this time will be treated as an error.
Note
1) If the node does not send a response within the maximum node response
time, a response timeout error will occur and an error message will be dis-
played.
2) Normally, the maximum node response time can be set to the default (5 se-
conds). If, however, a response timeout error frequently occurs, take one of
the following actions:
Increase the maximum node response time.