Connecting to a Node
36
b) Set DIP switch pin 5 to OFF and pin 7 to ON, and set the PC Setup word
DM 6650 (peripheral port settings) to 0000 Hex (standard setting). Set
the baud rate for the Controller Link Support Software to 9,600 bps.
c) Set DIP switch pin 5 to OFF and pin 7 to ON, and set the PC Setup word
DM 6650 (peripheral port settings) to 0001 Hex (settings as in DM 6651).
Set the communications settings (DM 6651: peripheral port settings) to
the same settings as the Controller Link Support Software. Set the baud
rate for the Controller Link Support Software to a value in the range 2,400
to 19,200 bps.
Connecting to RS-232C Port
Use one of the following methods when connecting to the RS-232C port on the
CPU Unit.
a) Set DIP switch pin 5 to ON, and set the baud rate for the Controller Link
Support Software to 9,600 bps.
b) Set DIP switch pin 5 to OFF, and set the PC Setup word DM 6645
(RS-232C port settings) to 0000 Hex (standard setting). Set the baud
rate for the Controller Link Support Software to 9,600 bps.
c) Set DIP switch pin 5 to OFF, and set the PC Setup word DM 6645
(RS-232C port settings) to 0001 Hex (settings as in DM 6646). Set the
communications settings (DM 6646: RS-232C port settings) to the same
settings as the Controller Link Support Software. Set the baud rate for
the Controller Link Support Software to a value in the range 2,400 to
19,200 bps.