5-3
Section
L: Data Link
78
1, 2, 3...
1. Select “R: Start/Stop” from the Data Link Menu.
2. Select “R: Start” to start the data links or “S: Stop” to stop the data links.
Example for “R: Start”
3. Specify the node to start or stop the data links. Use the Cursor Keys to move
the cursor to each field (“PC ID,” “Network address,” and “Node address”),
then enter a numeric value with Numeric Keys (enter a PC ID with Alphanu-
meric Keys).
Press the Enter Key to register the input item and move the cursor to the next
field.
Item
Meaning
PC ID
Enter the PC ID of the node.
Use this field only when a PC ID is to be used. If a PC ID is
used, the network address and node address will be specified
automatically (see page 124).
Network address
Enter the network address of the node.
The setting range is between 0 and 127.
Network address 0 represents the local network (the address
of the network containing the node to which the Controller
Link Support Software is connected). (see note)
For CS1-series, CVM1, or CV-series PCs with multiple
Communications Units, specify the network address explicitly.
Node address
Enter the node address of the node.
The setting range is between 0 and 62.
Node address 0 represents the local node (the address of the
node to which the Controller Link Support Software is
connected).
Note For CVM1 or CV-series CPU Units manufactured before April 1996
(lot No.: 
jj
46), always set routing tables. Specify in the “Network
address” the value (other than 0) specified in the routing tables. Refer
to the Controller Link Units Operation Manual (W309) for details.
Press the F10 (End) Key to cancel the data link start/stop procedure.
4. Press the F6 (Execute) Key. The data links for the specified network will be
started or stopped.
5-3-14 Displaying Data Link Status — M: Monitor Status
“M: Monitor status” is used to check data link operations.
Item
Meaning
Page
S: Monitor Data Link
status
Displays data link operating status for
the specified node.
79