Omron FQM1-CM001 用户手册

下载
页码 414
172
Pulse Outputs
Section 7-6
 
Pulse output 
operation mode 
(Only in 
Independent Mode)
Description
Compatible instructions
(1)
Relative pulse output
Positions to a relative position from the present position. 
The number of output pulses (actual output amount) in 
the specified direction is the target number of pulses.
• The frequency can be changed during pulse output.
• The direction and the target number of pulses cannot 
be changed during pulse output.
PULS(886) + SPED(885) or 
PULS(886) + ACC(888)
(PULS(886) sets the number of pulses 
and SPED(885) or ACC(888) starts the 
pulse output.)
PLS2(887)
(Sets number of pulses and starts 
pulse output.)
(2) (3)
Absolute pulse out-
put
Positions to an absolute position from the origin.
The number of output pulses is calculated automatically 
from the difference between the present position (pulse 
output PV) and target pulse amount.
Number of output pulses (actual output amount) =
|Present position 
− Target position|
• The frequency can be changed during pulse output.
• The direction and the target number of pulses cannot 
be changed during pulse output.
---
(2) Linear mode
Operates as linear counter with pulse 
output values ranging from 8000 0000 
to 7FFF FFFF hex.
Same as for (1).
(3) Circular 
mode
Operates as circular counter with pulse 
output values ranging from 0000 0000 
to the circular value.
When the pulse output PV exceeds the 
circular value, it is automatically 
returned to 0000 0000. Conversely, 
when the pulse output PV is decre-
mented from 0000 0000, it is automati-
cally returned to the circular value.
PULS(886) + SPED(885) or 
PULS(886) + ACC(888)
(PULS(886) sets the number of pulses 
and SPED(885) or ACC(888) starts the 
pulse output.)
(4)
Electronic cam con-
trol (linear)
(5)
Electronic cam con-
trol (circular)
Positions to an absolute position from the origin.
The difference between the present position (pulse output 
PV) and target pulse amount is calculated automatically.
Number of output pulses (actual output quantity) =
|Present pulse position 
− Target position|
• The direction is recognized automatically (CW direction 
when the present position < target position, and CCW 
direction when the present position > target position).
• The frequency and target position can be changed dur-
ing pulse output. The pulse output will stop if the direc-
tion is changed during pulse output.
PULS(886) (Sets the number of pulses 
and starts the pulse output.)
ACC(888)
PLS2(887)