MID-7654/7652 Servo Power Motor Drive User Guide
Inhibit Input Polarity Setting
Use DIP switch 1 on the 4-position DIP switch bank to globally set the
polarity for the inhibit input for all axes. Refer to Figures 1 and 3 for the
location of this switch.
polarity for the inhibit input for all axes. Refer to Figures 1 and 3 for the
location of this switch.
The factory-default setting of DIP switch 1 is active-low. If the inhibit input
is active, the axis is inhibited and the yellow status LED (middle row)
corresponding to that axis illuminates. Table 2 shows the DIP switch setting
for the inhibit input polarity selection.
is active, the axis is inhibited and the yellow status LED (middle row)
corresponding to that axis illuminates. Table 2 shows the DIP switch setting
for the inhibit input polarity selection.
Inhibit Output Polarity Setting
Use DIP switch 2 on the 4-position DIP switch bank to globally set the
polarity for the inhibit output for all axes. Refer to Figures 1 and 3 for the
location of this switch.
polarity for the inhibit output for all axes. Refer to Figures 1 and 3 for the
location of this switch.
The factory-default setting of DIP switch 2 is active-high. Table 3 shows
the DIP switch setting for the inhibit output polarity selection.
the DIP switch setting for the inhibit output polarity selection.
Table 2. Inhibit Input Polarity DIP Switch Settings
Switch Setting
Operation
Active-high
Active-low
(factory default)
Table 3. Inhibit Output Polarity DIP Switch Settings
Switch Setting
Operation
Active-high
(factory default)
Active-low