Mitsubishi Electronics Mitsubishi Digital Electronics Portable Multimedia Player GOT1000 用户手册

下载
页码 754
5 - 30
5. BUS CONNECTION
5.3 GOT Side Settings
5.3 GOT Side Settings
5.3.1
Setting communication 
interface (Communication 
settings)
Set the channel of the connected equipment.
1.
Select [Common] 
 [Controller Setting] from the 
menu.
2.
The Controller Setting window is displayed. Select the 
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: Mitsubishi
• Controller Type: Set the option according to the 
Controller Type to be connected.
• I/F: Interface to be used
• Driver: Set either of the following option according 
to the Controller Type to be connected.
BUS (Q)
BUS (A/QnA)
4.
The detailed setting is displayed after Manufacturer, 
Controller Type, I/F, and Driver are set.
Make the settings according to the usage 
environment.
Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be 
confirmed in [I/F Communication Setting].
For details, refer to the following.
5.3.2
Communication detail settings
(1) Bus(Q)
*1
This range is effective when collecting a large amount of 
data (such as logging and recipe function) on other than the 
monitor screen.
However, the range may affect the sequence scan time 
when connecting to Q00UJ/Q00U/Q01U/Q02UCPU or Q00J/
Q00/Q01CPU.
If you want to avoid the influence on the sequence scan time, 
do not set [High].
(This setting hardly affects QCPUs other than the above.)
*2
Set this range if you want to avoid the influence on the 
sequence scan time further than the [Normal] setting when 
connecting to Q00UJ/Q00U/Q01U/Q02UCPU or Q00J/Q00/
Q01CPU.
However, the monitor speed may be reduced.
(2) Bus(A/QnA)
2.
3.
4.
Click!
Item
Description
Range
Number of 
Stages
(Default: 1)
1 to 7
Slot No.
(Default: 0)
0 to 9
Monitor Speed
Set the monitor speed of the GOT.
This setting is not valid in all systems.
(Default: Normal)
High
*1
/Normal/
Low
*2
Timeout Time 
(Sec.)
Set the time period for a 
communication to time out.
(Default: 12)
12 to 90
Item
Description
Range
Number of 
Stages
(Default: 1)
1 to 7
Slot No.
(Default: 0)
0 to 7
Timeout Time 
(Sec.)
Set the time period for a 
communication to time out.
(Default: 3)
3 to 90