8. ETHERNET CONNECTION
8.3 GOT Side Settings
POINT
POINT
POINT
(1) Example of [Ethernet setting]
For examples of [Ethernet setting], refer to the 
following.
(2) Parameter reflection function of MELSOFT 
Navigator
(a) The color of the cells for the items which are 
reflected to GT Designer3 from MELSOFT 
Navigator changes to green. Set items, which 
are displayed in green cells, from the 
MELSOFT Navigator.
(b) When the settings of N/W No., PLC No., type 
or IP address are reflected to the parameter 
from the MELSOFT Navigator, those settings 
are added. Items set in advance are not 
deleted. However, if the combination of the N/ 
W No. and the PLC No. or the IP address 
overlaps, the item set in advance is 
overwritten.
(3) Changing the host on the GOT main unit 
The host can be changed by the utility function of 
the GOT main unit. For the detailed connection 
method, refer to the following manual.
User's Manual of GOT used.
(When using GT16)
8.3.4
Routing parameter setting
Up to 64 [Transfer Network No.]s can be set.
However, the same transfer network number cannot be set 
twice or more (multiple times).
Therefore, the one that can access to other station from the 
request source host GOT is 64 kinds of [Transfer Network 
No.]s.
POINT
POINT
POINT
Routing parameter setting
When communicating within the host network, routing
parameter setting is unnecessary.
For details of routing parameters, refer to the following
manual.
Q Corresponding Ethernet Interface Module 
User's Manual (Application)
*1
When accessing to other networks relaying a Build-in 
Ethernet port CPU, set the virtual network No. and PLC No. 
set in the Ethernet settings on GT Designer3.
Item
Range
Transfer Network No.
1 to 239
Relay Network No.
*1
1 to 239
Relay Station No.
*1
1 to 64