8. ETHERNET CONNECTION
8.4 PLC Side Setting
(1) Controller setting
(2) Ethernet setting
*1
Set the same value as that of GOT N/W No.
*2
Set a value different from that of the GOT PLC No. and the 
PLC No. of other PLCs on the same network.
Checking communication state of C 
Controller module
(1) When using the Command Prompt of Windows
.
Execute a Ping command at the Command Prompt of 
Windows
.
(a) When normal communication
C:\>Ping 192.168.0.1
Reply from 192.168.0.1: bytes=32 time
<10ms TTL=32
(b) When abnormal communication
C:\>Ping 192.168.0.1
Request timed out.
(2) When abnormal communication
At abnormal communication, check the followings and 
execute the Ping command again.
• Cable connecting condition
• Confirmation of switch and network parameter setting
• Operation state of PLC CPU (faulty or not)
• The IP address of C Controller module specified in the 
ping command
8.4.5
Connecting to Ethernet 
module (QnA Series)
This section describes the settings of the GOT and 
Ethernet module (QnA Series) in the following case of the 
system configuration.
POINT
POINT
POINT
Ethernet module (QnA Series)
For details of the Ethernet module (QnA Series), refer
to the following manual.
For QnA Ethernet Interface Module User’s 
Manual
System configuration
*1
The Ethernet module is mounted on the base unit slot 0.
The Start I/O No. of the Ethernet module is set to "0".
Item
Set value (Use default value)
GOT NET No.
1
GOT PLC No.
1
GOT IP Address
192.168.3.18
GOT Port No. (Communication)
5001
GOT Port No.
(Ethernet Download)
5014
Default Gateway
0.0.0.0
Subnet Mask
255.255.255.0
Retry
3times
Startup Time
3sec
Timeout Time
3sec
Delay Time
0ms
Item
Set value
Ethernet setting 
No.1
Host
*
-
N/W No.
1
*1
1
*1
PLC No.
2
*2
3
*2
Type
QnD(H)CCPU
QnD(H)CCPU
IP address
192.168.3.1
192.168.3.2
Port No.
5006 (fixed)
5006 (fixed)
Communication
UDP (fixed)
UDP (fixed)
<GOT>(The settings other than 
the following are set to the default)
Network No.
: 1
PLC No.
: 1
IP address
: 192.168.0.18
Port No.
: 5001
Communication format
: UDP(fixed)
Network No.
: 1
PLC No.
: 2 
Port No.
: 5001
Communication format
: UDP(fixed)
<Ethernet module>  (The settings other than
the following are set to the default)
*1
IP address
: 192.168.0.19
■