8. ETHERNET CONNECTION
8.4 PLC Side Setting
8.4.8
Connecting to Display I/F 
(CNC C70)
This section describes the settings of the GOT and Display 
I/F (CNC C70) in the following case of the system 
configuration.
POINT
POINT
POINT
Display I/F (CNC C70)
For details of the Display I/F (CNC C70), refer to the
following manual.
C70 Series SET UP MANUAL
System configuration
IP address settings of CNC C70
(1) Remote monitor tool
: Necessary  : As necessary   : Not necessary
(2) CNC monitor
: Necessary  : As necessary   : Not necessary
(3) Communication check
The CNC C70 can communicate with the GOT when 
INIT.LED of the CNC C70 is lit.
For confirming the communication state, refer to the 
following.
[Controller Setting] and [Ethernet] of GT 
Designer3
(1) Controller setting
Item
Set value
Setting necessity at 
GOT connection
IP address
192.168.0.19
Subnet mask
255.255.255.0
Gateway address
0.0.0.0
Port number
64758 (fixed)
Speed auto/10M
0 (fixed)
<GOT> (The settings other than the 
following are set to the default)
Network No.
: 1
PLC No.
: 1
IP address
: 192.168.0.18
Port No.
: 5001
Communication format : UDP (fixed)
Network No.
: 239
PLC No.
: 2
IP address
: 192.168.0.19
Port No.
: 5001
Communication format
: UDP(fixed)
<Q17nNCCPU> (The settings other than the
following are set to the default)
■ 
Item
Set value
Setting necessity at 
GOT connection
IP address
192.168.0.19
Subnet mask
255.255.255.0
Gateway address
0.0.0.0
Port number
64758 (fixed)
Speed auto/10M
0 (fixed)
Item
Set value (Use default value)
GOT NET No.
1
GOT PLC No.
1
GOT IP Address
192.168.0.18
GOT Port No. 
(Communication)
5001
GOT Port No. 
(Ethernet Download)
5012
Default Gateway
0.0.0.0
Subnet Mask
255.255.255.0
Retry
3times
Startup Time
3sec
Timeout Time
3sec
Delay Time
0ms