8. ETHERNET CONNECTION
8.4 PLC Side Setting
8.4.10 Connecting to PERIPHERAL 
I/F (Built-in Ethernet port 
Motion Controller CPU)
This section describes the settings of the GOT and Built-in 
Ethernet port Motion Controller CPU in the following case 
of system configuration.
POINT
POINT
POINT
(1) GOT type setting
For details, refer to the following.
(2) CPU No. specification of Q170MCPU
Set whether to monitor the PLC CPU area or the 
Motion CPU area of Q170MCPU, in the CPU No. 
specification. For details, refer to the following.
(3) PLC type of GX Works2/GX Developer
When creating a program, set the following PLC 
type:
• For Q173D(S)CPU/Q172D(S)CPU
QnUD(E)(H)CPU
• For Q170MCPU
Q03UDCPU
(4) Built-in Ethernet port CPU
For details of Built-in Ethernet port CPU, refer to 
the following manual.
User's Manual of Q173D(S)CPU/
Q172D(S)CPU and Q170MCPU
System configuration
Leave the Built-in Ethernet port Motion Controller CPU 
settings as default in the following system 
configuration.
*1
For the settings when using system devices including a hub 
and a transceiver, refer to the following.
*2
These setting items do not exist at the PLC side. However, 
the virtual values must be set on the GOT side.
Basic setting of MT Works2
Use the default values of the basic setting for the 
system configuration above.
(1) Built-in Ethernet port
Item
Set value
Setting necessity 
at GOT 
connection
IP address
192.168.3.39
(Default)
Subnet mask pattern
-
Default router IP address
-
<GOT>
(The settings other than the 
following are set to the default)
*1
*2
*2
Network No.
: 1
PLC No.
: 1
IP address
: 192.168.3.1
Port No.
: 5001
Communication 
format
: UDP (fixed)
Network No.
: 1 (virtual)
PLC No.
: 2 (virtual)
IP address
: 192.168.3.39
Open system
: MELSOFT connection (fixed)
<Connecting to Built-in Ethernet port CPU>
(The following settings are set to the default)
■