Mitsubishi Electronics Mitsubishi Digital Electronics Portable Multimedia Player GOT1000 用户手册

下载
页码 754
13 - 12
13. CC-Link CONNECTION (INTELLIGENT DEVICE STATION)
13.4 PLC Side Setting
13.4 PLC Side Setting
The GOT operates as the stations of which are shown 
below in the CC-Link system.
The switch settings and parameter settings of the PLC side 
(CC-Link module) are described in 13.4.1 to 13.4.7.
HINT
HINT
HINT
Number of stations occupied
The number of stations occupied is setting for 
determining number of link device points (RX/RY/
RWw/RWr) used by the GOT.
To use multiple numbers of link device points in the 
case of cyclic transmission between the GOT and CC-
Link module, set the number of stations occupied as 
the exclusive station 4.
The number of link device points at the exclusive 
station 1 and 4 is shown below.
CC-Link Ver.2
CC-Link Ver.1
Station data
Description
Station type
Intelligent device station, Ver.1 intelligent device 
station or Ver.2 intelligent device station
Number of stations 
occupied
Station 1 or Station 4
Model name
Refer to
CC-Link
module
(Q Series)
Connecting 
with
Ver.1 
compatible
QJ61BT11, 
QJ61BT11N
Connecting 
with Ver.2 
compatible
QJ61BT11N
Connecting 
with Ver.1/
Ver.2 
compatibles 
mixed
QJ61BT11N
CC-Link module
(QnA Series)
AJ61QBT11, 
A1SJ61QBT11
CC-Link module
(A Series)
AJ61BT11, 
A1SJ61BT11
Link
device
Expanded cyclic setting
Single
Double
Quadruple
Octuple
Exclu
sive 
statio
n 1
Exclu
sive 
statio
n 4
Exclu
sive 
statio
n 1
Exclu
sive 
statio
n 4
Exclu
sive 
statio
n 1
Exclu
sive 
statio
n 4
Exclu
sive 
statio
n 1
Exclu
sive 
statio
n 4
Remote 
input (RX)
32 
points
128 
points
32 
points
224 
points
64 
points
448 
points
128 
points
896 
points
Remote 
output (RY)
32 
points
128 
points
32 
points
224 
points
64 
points
448 
points
128 
points
896 
points
Remote 
register 
(RWw)
points
16 
points
points
32 
points
16 
points
64 
points
32 
points
128 
points
Remote 
register 
(RWr)
points
16 
points
points
32 
points
16 
points
64 
points
32 
points
128 
points
Link device
Number of stations occupied
Exclusive station
Exclusive station 4
Remote input (RX)
32 points
128 points
Remote output (RY)
32 points
128 points
Remote register (RWw)
4 points
16 points
Remote register (RWr)
4 points
16 points