Mitsubishi Electronics Mitsubishi Digital Electronics Portable Multimedia Player GOT1000 用户手册

下载
页码 754
22. FA TRANSPARENT FUNCTION
22.6 Personal Computer Side Setting
22 - 55
17
ROBOT  CONT
ROLLER 
CONN
E
C
T
ION
18
CNC CONNECTION
19
GOT
 MUL
T
I-
DROP
 
C
O
NNECTION
20
MUL
TIPLE-G
T14
, GT
12, 
GT1
1, G
T10 
C
O
NNEC
TI
O
N FUNCTIO
N
21
MUL
T
I-CHANNEL
 
FUN
C
TIO
N
22
F
A
 TRANSP
A
R
E
N
FUNC
TION
22.6.6 Accessing by the MT Works2
This section explains the procedure to set the FA 
transparent function of MT Works2 with an example of 
connecting to motion controller CPU (Q series).
When connecting the GOT and personal 
computer with serial or USB
(1) Connecting the GOT and PLC in bus connection or 
direct CPU connection
1.
Click [Transfer setup] 
 [Online].
2.
The [Transfer setup] is displayed.
3.
Set the [Transfer setup]:
PC side I/F
: Serial USB
CPU side I/F
: GOT
Other Station Setting : No specification
4.
Double-click [Serial] of the PLC side I/F to display [PC 
side I/F Serial setting].
5.
Check-mark either of the following in [PC side I/F 
Serial setting].
Mark the [RS-232C] checkbox.
Mark the [USB] checkbox.
When connecting the GOT and PC with serial
When connecting the GOT and PC with USB
6.
Double-click [GOT] of the CPU side I/F to display 
[CPU side I/F Detailed Setting of GOT].
7.
Check-mark either of the following in [CPU side I/F 
Detailed Setting of GOT].
Mark the [via GOT(Bus) transparent mode] checkbox.
Mark the [via GOT (direct coupled) transparent mode] 
checkbox.
8.
The screen returns to [Transfer setup]. Click 
[Connection Test] to check if MT Works2 has been 
connected to the motion controller (Q mode).
Bus connection
Direct CPU connection