LST AC-58000-300 产品宣传页

下载
页码 1
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
AC-58000-300_DBL_LST_EN_0804.PDF • PAGE 1
A
Building Safety. Building Security.
Description
•   ADM loop technology with
Apollo/Discovery protocol
•   Ideal supplement to common smoke 
detectors
•   Sensitivity selectable in 5 steps
•   Optional connection of remote 
indicator
•  Sealed electronics
The Carbon Monoxide Detector AC-58000-300 uses a 
durable electrochemical CO sensor. It is an ideal sup-
plement to common smoke detectors because it is in-
sensitive to the usual vapors and household products, 
in low concentrations. The carbon monoxide detector 
does  not  respond  to  smoke  particles  and  heat,  and 
therefore it shall only be used in addition to smoke or 
heat detectors. Besides, the size of the fi re area shall 
not exceed 50m
2
.
The proven ADM loop technology with Apollo/Discovery 
protocol establishes a permanent communication bet-
ween the fi re detection control panel and the detector. 
That ensures a periodical function testing of the detec-
tor.
The two LEDs with 360° visibility indicate the activated 
condition of the detector. The detector address is se-
lected by means of a code card in the detector base. 
Therefore the detector can be changed without additi-
onal tools.
The detector can be attached to different types of ba-
ses, and it can be protected against theft.
Specifi cations
Operating voltage 
Supply through loop voltage
Current consumption 
typ. 400µA (quiescent)
Ambient temperature 
0°C to +40°C (no condensation)
Relative humidity 
15 – 90% (no condensation)
Dimensions ø × H 
100 × 42 (mm)
Colour 
white
Weight 
105g
Order number 
243100
Order name 