Liebert Universal Monitor 用户手册

下载
页码 144
Default Settings Quick Reference Guide
134
Table 39
Expansion Board - default settings for inputs and outputs
Feature
Default
Other Options
LABEL
INPUT_09 - INPUT_24
Any name (up to eight characters)
NORM OPEN/CLOSE
NO (Normally open)
NC (Normally closed)
ALARM/EVENT
AL (Alarmable)
EV (Event)
LATCHED
NL (Unlatched) / N (No)*
L (Latched) / Y (Yes)*
DELAY
00:01 (1 second)
Any time (in minutes and seconds) from 00:00 to 99:59
NOTE: Different abbreviations are used to designate a digital input as Latched or Unlatched.
Digital input
By default, mapped to digital output:
Input_09
(none)
Input_10
(none)
Input_11
(none)
..
.
(none)
Input_24
(none)
NOTE: By default, no Expansion Board inputs are mapped to any outputs.
Feature
Default
Other Options
LABEL
OUTPUT09 - OUTPUT16 Any name (up to eight characters)
Table 40
Expansion Board - other default settings
Feature
Default
Other Options
SETUP EXP BOARD (IS THE 
EXPANSION BOARD 
CONNECTED?)
N (Not connected)
Y (Connected)
DIP SWITCH SETTINGS
Feature
Default
Other Options
S1 Digital output DIP switches
Off (NO - Normally Open) On (NC - Normally Closed)
OTHER SWITCH SETTINGS
Feature
Default
For all switches:
1 = ON, 0 = OFF
Other Options
SW1 (factory configured)
11111111
SW2 (factory configured)
11111111
SW3 (factory configured)
10000100
SW4 (factory configured)
10000100
JUMPER SETTINGS
Feature
Default
Other Options
JP2 (factory configured)
Left two pins jumpered
JP3 (factory configured)
Left two pins jumpered
JP4 (factory configured)
Left two pins jumpered
JP5 (factory configured)
Bottom two pins jumpered —