RC3000 Antenna Controller 
Chapter 3 
Detailed Operation 
 
 113  
 
 
3.3.1.3.5 Elevation Pot Drive 
                          CONFIG-EL POT 
FAST/SLOW:  0.5     COAST: 0.3 
MAX ERROR: 0.01     TRIES:  3 
SET THRESHOLD <0.0-10.0 DEGREES> 
The CONFIG_EL POT screen contains configuration items for calibrating elevation movements based on 
potentiometer position feedback.  See the Drive System theory section 1.3.7. 
FAST/SLOW:   
SET THRESHOLD <0.0-10.0 DEGREES> 
During an automatic move, the elev_fast_slow_threshold configuration item is used to set the number of 
degrees before a target position is reached, when the controller switches the speed of the drive from fast 
to slow.    
MAX ERROR:   
SET MAXIMUM ERROR <0.01 - 1.00 DEGREES> 
The elev_max_position_error configuration item sets the maximum acceptable error between the final 
resting position and a target position during an automatic move. 
COAST: 
 
SET COAST RANGE <0.0 - 2.0 DEGREES> 
During an automatic move, the elev_coast_threshold configuration item sets the number of degrees 
before the target position is reached where the drive will be deactivated.  The idea is to deactivate the 
drive and let the antenna coast into position.  If prior to the initiation of the move operation, the total 
number of degrees that the actuator has to move to reach the target position is less than the 'Coast 
Threshold
, the drive will be deactivated when its position is within 'Max Position Error of the target 
position.  
 
RETRY: 
 
SET MAX NUMBER OF TRIES <0-10> 
The elev_auto_move_max_retry_cnt configuration item sets the maximum number of attempts which will 
be made to hit a target position (within Max Error  - described above) during an automatic move based 
on potentiometer feedback.