HP Performance Optimized Data Center (POD) 240a 用户手册

下载
页码 93
 
Environmental control system  47 
 
Operation displayed 
Description 
Isolation damper 
Indicates the position of the isolation damper, 
100% means the damper is open 
Water PID 
Indicates the percentage of full flow water usage  
Return damper 
Indicates the position of the return damper, 100% 
means the damper is open 
Bypass damper 
Indicates the position of the bypass damper, 
100% means the damper is open 
Cold aisle fan 
Indicates the speed of the cold aisle fan 
Outdoor damper 
Indicates the position of the return damper, 100% 
means the damper is open 
OA temperature 
Indicates the OA temperature 
OA relative humidity 
Indicates the OA relative humidity 
OA dew point 
Indicates the OA dew point temperature 
The AD detail screen displays the following alarm conditions: 
 
Alarm displayed 
Description 
Filter 
Indicates that a filter needs to be changed 
Fire/smoke 
Indicates fire or smoke is detected 
Hi water warning 
Indicates water in the Adiabatic drain pan 
Hi-Hi water critical 
Indicates excessive water in the Adiabatic drain 
pan 
Heater over temperature 
Indicates the AHU heater temperature is too high 
AC power failure 
Indicates the AHU power is in failure 
CA temperature compare  Indicates the AHU discharge temperature is in 
range of the other AHUs in the IT section 
Winterize 
Indicates the Adiabatic units are operating in 
Winterize mode 
 
If an alarm condition exists for the Adiabatic unit, the parameter that is out of range will turn amber or red, 
based on the severity of the alarm condition. For more information about alarm conditions, see "Alarms 
screen (on page 
)". 
To view the details of another Adiabatic unit, click the PREV/NEXT buttons on the top of the screen. These 
buttons allow you to scroll numerically through all of the Adiabatic units. 
 
Charts screen 
The Charts screen displays the following information: 
 
Psychrometric chart (on page 
)—Displays recommended and operational ranges for the HP POD 
240e NA. 
 
Readings chart (on page 
)—Displays static pressure, temperature, fan speed, water valve, or 
damper readings.