Site plan requirements and actions  24 
 
General assembly equipment locations 
 
Lifting requirements 
  
 
WARNING:
  The only approved method for lifting any section of the HP POD 240e NA is the use 
of a spreader bar or harness. Lifting any section of the HP POD 240e NA in any other way can 
cause damage to the HP POD 240e NA and void your warranty. The harness and lifting 
connections must be perpendicular to the lifting blocks or connections. 
  
 
Storage requirements 
If the site is not ready for assembly and operation, determine a location for storage when creating the site 
plan. 
  
 
CAUTION: 
 The HP POD 240e NA must maintain 20% relative humidity to minimize 
condensation and oxidation within the HP POD 240e NA. 
  
  
 
CAUTION: 
 While being stored, the HP POD 240e NA must be kept in a level position even if 
stored on a trailer. 
  
Changes in ambient temperatures can cause condensation in a non-operational HP POD 240e NA. If the HP 
POD 240e NA is placed in storage or is in non-operating mode for over 72 hours, HP recommends using one 
of the following methods to minimize condensation and oxidation within the HP POD 240e NA: 
 
Desiccant unit 
 
Desiccant material 
 
Heater with a fan 
 
Air conditioner with a heater strip 
Consult with HP Services to determine the most effective method. 
 
Other structures 
If you provide a vestibule or other structure that will be installed at the HP POD 240e NA site, you must 
maintain the following specifications: 
 
Flashing must be installed on the exterior of the HP POD 240e NA in the location where the other 
structure will be attached to protect the HP POD 240e NA and be sure that there is a waterproof barrier. 
 
Access catwalks and landings might be required to maintain the required egress from the HP POD 240e 
NA HVAC service area. 
 
Access catwalks and landings might be required to maintain the required access to the HP POD 240e 
NA electrical panels.