DR4300 Circular Chart Recorder 
174 
DR4300 Circular Chart Recorder Product Manual 
12/03 
8.3 Self Diagnostics 
8.3.1  Power up tests 
Tests run automatically 
When the recorder is powered-up, self-diagnostics are run by the software.   
As the tests in Table 8-2 are run, the display indicates whether the tests were passed or failed as described 
below.  
   
Table 8-2  Power-Up Diagnostic Tests 
Lower Display 
Upper Display 
RAMTST 
PASS or FAIL 
CFGTST (configuration checksum) 
PASS or FAIL 
CALTST (working calibration) 
PASS or FAIL 
 
Status of tests displayed 
As the tests are run, the lower line of the display shows which test is running. The upper line of the display 
indicates the status. If any of these tests fail, “FAIL” appears momentarily in the upper display, then a 
display test is run. The display changes to show the value of the process variable on the top line, and the 
error message for the failed test on the second line.  
In addition, if the control group parameter “CONTRL” has a value of “ENAB” when the test is failed, the 
message “FAILSF” (failsafe) will alternate with error message for the test, and the controller will be in 
manual mode. When the “FAILSF” message is displayed, it indicates that the recorder control output has 
been driven to the value assigned to the control group “FAILSF” parameter.  
By default, when the recorder is powered up the display will be for pen 1. Therefore, when the power up 
tests run, the “PASS” and “FAIL” messages will apply only to the printed circuit assembly associated with 
pen 1. However, in a 2-pen recorder the tests will also be run on the printed circuit assembly for pen 2. If 
the pen 2 assembly fails one of the tests, the message “P2 ERR” will be displayed, along with any error 
messages from the pen 1 tests.