Honeywell Network Hardware NETAXS-123 用户手册

下载
页码 76
Installing the NetAXS-123 Panels
Panel Components and Descriptions
NetAXS-123 Access Control Unit  Installation GuideDocument 800-05779, Revision A
9
Note:  
For NetAXS-123 reader specifications, see 
2.2.3  Real-Time Clock Protection
The panel RTC is backed up using a super capacitor. The super capacitor will power the real-time 
clock for 24 hours in the absence of primary power or backup battery.
2.3  Power Supply
The NetAXS-123 Compact Enclosure is powered by Power Over Ethernet (PoE) injector. This PoE 
injector can supply a total system current of 800mA to 900mA @ 12VDC. However the NetAXS-123 
controller board consumes 400mA of current, and it therefore leaves 450mA of total current for the 
12VDC external power. See 
, page 60, for further details on current limits 
using PoE. 
The Standard Enclosure uses a 12VDC 4A power supply with an international input of 100VAC to 
240VAC. The supply also charges and monitors the condition of the battery. Wire the unswitched 
electrical power to the supply per the National Electrical Code as well as any local electrical codes, 
including the safety ground wire.
An input power indicator is supplied, and it is illuminated when input voltage is present. If the 
indicator is off, the input voltage is off, or too low to operate the system. 
Caution: 
Disconnect the battery and AC power before servicing the fuse. For continued protection 
against the risk of electric shock and fire hazard, replace the input fuse with a GMA type fuse with the 
rating of 1A, 250V. The fuse is located in the lower-left corner in the cabinet, as shown below.
OmniAssure
OT30
OT30HONA
OT31
OT31HONA
OT35
OT35HONA
OT36
OT36HONA
OT70
OT70HONA
OT75
OT75HONA
NexWatch
DR 4200K
92042000000
DR 4220
92042200000
Series
Reader Model
Honeywell Part 
Number