Installing the NetAXS-123 Panels
Installation
5. When the installation is complete, the closing screen appears:
6. Click 
Finish
.
7. Connect the computer to the NetAXS-123 controller with a USB-A to Micro USB-B cable.
8. Turn on the power to the NetAXS-123 controller.
For login information, go to https://192.168.2.150.
3.7.2  RS-485 Communications
If a NetAXS-123 panel is to be placed onto a prexisting RS-485 dropline loop (NetAXS) it must be 
setup as the Gateway panel. The interface allows the wiring of a Multidrop communication network of 
up to 4,000 feet (1200 m) in length. Only one host converter device per dropline is supported. 
Note:  
NetAXS-123 must be the Gateway panel on an existing NetAXS loop. The NetAXS-123 panel 
cannot be placed as a Downstream panel when the Gateway is a NetAXS system. 
DIP switch position 6 on the NetAXS-123 panel selects whether the panel is a Gateway or 
Downstream panel. The switch in the OFF position configures the panel as a Downstream panel; ON 
configures a Gateway. The panel must be power cycled for a new switch setting to be recognized.
 
DIP 
switch positions 1-5 are used to select the panel’s address on the network. Refer to 
switch setting information.