Honeywell Galaxy 3-48C 安装指导
Galaxy 3 Series Installation Manual
2-9
Stand-by Battery
The Galaxy 3 Series control panels can accommodate up to 2 x 17 Ahr batteries. Ensure that the battery
connector leads on the control panel Powers Supply Unit (PSU) are connected to the correct terminals on the
battery.
connector leads on the control panel Powers Supply Unit (PSU) are connected to the correct terminals on the
battery.
CAUTION:
There is a risk of explosion if the battery is replaced by an incorrect type.
Dispose of used batteries according to the instructions.
Dispose of used batteries according to the instructions.
Table 2-3. Battery/Control Panel connections
Battery Start-up
The system can be powered up via the Battery Start-up jumper if there is no AC power. To do this, short
out the Battery Start-up jumper for the duration of the configuration process only. Never leave the Battery
Start-up connected or else deep discharge of the Stand-by Battery will occur.
out the Battery Start-up jumper for the duration of the configuration process only. Never leave the Battery
Start-up connected or else deep discharge of the Stand-by Battery will occur.
On-Board Power Supply Unit
The on-board Power Supply Unit (PSU) supplies and monitors power to the system and peripherals. The
following table shows the fuse name and value in amps.
G3-144/G3-520: The Galaxy 3 Series control panel contains four fuses. Details are given in the table below.
following table shows the fuse name and value in amps.
G3-144/G3-520: The Galaxy 3 Series control panel contains four fuses. Details are given in the table below.
NOTE: The G3-48 does not require fuse AUX2.
Table 2-4. On-board PSU Fuses
Power Monitoring Characteristics:
Low battery level: 11.2V
Deep discharge protection: 10.5V
Overvoltage protection: 14.7V
Deep discharge protection: 10.5V
Overvoltage protection: 14.7V
Stand-by Battery
l
e
n
a
P
l
o
r
t
n
o
C
y
r
e
t
t
a
B
T
A
B
-
l
a
n
i
m
r
e
t
e
v
-
T
A
B
+
l
a
n
i
m
r
e
t
e
v
+
FUSE NAME
VALUE (AMPS)
MONITORS
TYPE
AUX1
1.0
RS485 Line 1, RIO 0, Zones 1-8: +12V,
on-board comms
on-board comms
20 mm, anti-surge
AUX2
1.0
RS485 Line 2, RIO 1, zones 1-8 +12V
20 mm, anti-surge
BATT
1.6
Battery
20 mm, anti-surge
BELL
1.0
Outputs RIO 0 1-4, RIO 1 1-4, Horn output 20 mm, anti-surge
G3-48
The PSU total capacity is 1.5A. Internally the PSU
is split in two in order to ensure sufficient current is
always available for stand-by battery recharge.
The PSU capacity is broken down as follows:
The PSU total capacity is 1.5A. Internally the PSU
is split in two in order to ensure sufficient current is
always available for stand-by battery recharge.
The PSU capacity is broken down as follows:
•
Battery:
0.75A
•
Control PCB:
0.25A
•
AUX +12V:
0.5A
G3-144/520
The PSU total capacity is 2.5A. Internally the PSU is
split in two in order to ensure sufficient current is al-
ways available for stand-by battery recharge.
The PSU capacity is broken down as follows:
The PSU total capacity is 2.5A. Internally the PSU is
split in two in order to ensure sufficient current is al-
ways available for stand-by battery recharge.
The PSU capacity is broken down as follows:
•
Battery:
1.25A
•
Control PCB:
0.25A
•
AUX +12V:
1.00A
The PSU is available for zones/outputs and peripherals.