Gossen Metrawatt 751 用户手册

下载
页码 48
12
GOSSEN METRAWATT GMBH
5
Classification of Devices Under Test
5.1
Safety Classes
Devices assigned to all of the following safety classes are equipped with 
basic insulation, and provide for protection against electrical shock by 
means of various additional precautions as well.
Safety Class I Devices 
Exposed, conductive parts are connected to the protective conductor so 
that they are not charged with voltage if the basic insulation should fail.
Safety Class II Devices 
These devices are equipped with double insulation or reinforced 
insulation.
Safety Class III Devices 
These devices are powered with safety extra-low voltage (SELV). Beyond 
this, no voltages are generated which exceed SELV. These devices may 
not be connected to the mains.
Note: The DUT may only be connected to the test instrument at jacks 1 
through 3 (Feature F01). Only a visual inspection, an insulation resistance 
measurement or a measurement of the supply voltage can be performed, 
see parameter “SC III U
Parameter Classification (in the Sequence... menu)
The SECUTEST
®
SII always tests in accordance with the strictest limit val-
ues of the respectively selected safety class. The test is failed if this limit 
value is exceeded. However, devices under test exist for which higher limit 
values are allowable.
If parameter classification is activated (= x), the user is asked if higher limit 
values are allowable for the DUT. If “Yes” is entered, reevaluation ensues 
and the DUT may pass the test.
Examples
If the insulation resistance test is failed, or if interference suppression 
capacitors have been replaced, equivalent leakage current measurement 
must be performed on DUTs with heating elements in accordance with 
DIN VDE 0702. 
The test is failed by a DUT with 300 kW with deactivated classification 
function (= _), but it is passed with activated classification function (= x) if 
the question is answered accordingly.
Similar possibilities for passing the test, although it might otherwise be 
failed, are included in DIN VDE 0701, part 1.
If the DUT is connected via the jacks instead of the test socket, other limit 
values apply because higher power consumption is possible in this case 
(e.g. part 1 specifies a limit value of 1 mA per kW for equivalent leakage 
current).
 
5.2
Application Parts (electrical medical devices)
Type B Application Parts 
 (body)
Devices of this type are suitable for both internal and external patient 
applications, except for use in direct proximity to the heart.
These devices provide for adequate protection against shock especially 
as regards:
Reliable leakage current
Reliable protective conductor connection if utilized
Devices of the following safety classes are allowable: I or II.
Type BF Application Parts 
 (body float)
Same as type B, but with type F insulated application parts.
Type CF Application Parts 
 (cardiac float)
Devices of this type are suitable for use directly at the heart. The 
application part may not be grounded.
Devices of the following safety classes are allowable: I or II.