 Chapter 2: Installation        
17
If you are mounting the PM IPDU, obtain a Phillips screwdriver and appropriate nuts and bolts 
before starting the following procedure.
NOTE: When mounting a Cyclades PM IPDU zero U model to a wall stud, securely mount it by using a #10 or 
larger screw or use a drywall fastener rated min. 25 lb. (11.34 kg).
The following graphics depict the orientation of the brackets for front rack mounting PM IPDU.
Figure 2.1: Rack Mounting a Cyclades PM10 IPDU, PM10l IPDU and PM8iIPDU
Installation environment
When installing the PM IPDU, ensure that the following environment specifications are met.  
Bracket
Table 2.6: PM IPDU Optimum Installation Environment 
Environment Factor
Recommendation
Temperature
The manufacturer's maximum recommended ambient temperature for the 
Cyclades PM IPDU is 122 ºF (50 ºC).
Elevated Operating Ambient 
Temperature
If the Cyclades PM IPDU is installed in a closed or multi-unit rack assembly, 
the operating ambient temperature of the rack environment may be greater 
than room ambient temperature. Therefore, consideration should be given 
to installing the equipment in an environment compatible with the 
manufacturer’s maximum rated ambient temperature. See above.
Reduced Air Flow
Installation of the equipment in a rack should be such that the amount of air 
flow required for safe operation of the equipment is not compromised.
Mechanical Loading
Mounting of the equipment in the rack should be such that a hazardous 
condition is not achieved due to uneven mechanical loading.
Circuit Overloading
Consideration should be given to the connection of the equipment to the 
supply circuit and the effect that overloading of circuits might have on 
overcurrent protection and supply wiring. Appropriate consideration of 
equipment nameplate ratings should be used when addressing 
this concern.