CyberPower K01-0000207-00 产品宣传页

下载
页码 2
Environment Sensor
ENVIROSENSOR
User’s Manual
Package Contents
Flat Head Screw (M3x20)
with Plastic Nylon Anchor 
CAT5 RJ45 Ethernet Cable
(10 feet/3.05 m) 
ENVIROSENSOR
Hook and Loop Tape
Cyber
Power
Relia
bility. Qual
ity. Va
lue.
R
User'
s M
anua
l
User’s Manual
Product Features
K01-0000207-00 
Overview
The CyberPower environmental sensor (ENVIROSENSOR)
along with select SNMP/HTTP cards (RMCARDXXX) or most 
Switched and Monitored PDUs enables users to monitor the 
temperature and humidity of a server closet and/or datacenter 
remotely.  With CyberPower's PowerPanel Business Edition 
software, users can establish thresholds that will automatically 
notify users when an event has occurred via email, SMS and 
SNMP traps. Additionally, the ENVIROSENSOR provides 4 input 
dry contacts that enable users to monitor the status of connected 
devices, such as door switch sensors.
Features include:
• Real time environment monitoring
• Remote management and configuration of the sensor via Web 
Browsers or NMS
• Automatic events notification via email, SMS and SNMP traps
• 4 input dry contacts application interface provided
• Displays the name and location of the sensor and 
connected devices
A. LED
B. Input Dry Contact 1-4
C. Common Connection
D. RJ45 Port 
     (connect to RMCARD/PDU) 
NOTE: Please refer to Appendix 
for Input Dry Contact Application.
A
DATA
STATUS
COM
4
1
2
3
C
B
D
Technical Specification
Installation Guide
Method 1- Hook and Loop Tape 
Mounting
Step 1. Clean the surface of the 
area where the sensor will 
be installed. Apply one side 
of the hook and loop tape 
to the bottom of the sensor 
and the other side to the 
sensor location.
Step 2. Attach the sensor on the 
surface and hold for about 5 
seconds to ensure cohesion.
NOTE: Once the sensor is installed, 
you will want to leave it in place to 
ensure the the hook and loop tape 
maintains its adhesiveness.
Step 3. To connect the sensor with 
RMCARD/PDU, use the 
attached RJ45 Ethernet 
Cable. Plug one end into the 
RJ45 Port and the other end 
into the RMCARD/PDU.
NOTE: If the distance of 
RMCARD/PDU and the sensor is 
longer than 10 feet/3.05 m, use a 
standard RJ45 Ethernet Cable as 
needed (max 50 feet/15 m).
Universal
RX/TX
Link
RMCARD203
Copyright © 2011 CyberPower Systems, Inc.
                                    ENVIROSENSOR 
Input Voltage 
7V - 28V
 
Halt mode 72 mW/
Power Dissipation 
Normal mode 110 mW
 
(Default 12V input)
Measurement Range and Accuracy 
  Temperature 
32-158
℉ with accuracy ± 1.8℉/
 
0-70
℃ with accuracy ± 1℃
  Humidity 
10-90 RH with accuracy ± 2% 
Communication 
  Connection Port 
RJ45 Port
  Input Dry Contact 
4
Physical 
  Dimensions (L x W x H) 
2.32 x 1.77 x 1.14 inches/
 
59 x 45 x 29 mm
  Weight 
1.46 oz /41.5 g
Safety Approvals 
FCC Class B, CE, C-Tick
Warranty 