4)  When the furnace is installed in the horizontal configuration, the high limit 
and fan control must also be located in the upper position on the casing when the 
furnace is placed in the final installed position, refer to Figure 7. If the control 
must be relocated, remove the cover of the control to gain access to the 
mounting screws.  Remove the mounting screws and the control. Insert the 
control into the alternate mounting hole in the casing and mark the screw 
locations. Drill pilot holes for the new screws. Install the control in the new 
mounting location and secure it with the mounting screws. Replace the cover of 
the control. A metal, snap-in cap is furnished with the furnace to close the 
unused hole, for the control, in the casing.  
 
 
 
 
Figure 7: Correct locations for the horizontal furnace high limit and fan control.
 
 
20