FieldServer FS-8704-14 用户手册

下载
页码 30
FS-8704-14 EtherNet/IP Manual 
 
 
 
 
 
 
 
Page 26 of 30 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA   Web: www.fieldserver.com 
Tel: (408) 262 2299   Fax: (408) 262 2269   Toll Free: (888) 509 1970   email: support@fieldserver.com 
FieldServer Data Type 
Description (or Device Data Type)  
Analog  Input  Point  –  Class  Code 
0x0A 
Attributes Supported: 
Class Instance Support (0x00) 
Class Attributes: 0x02 (Max Instance) 
Two instances supported (0x01 and 0x02) 
Attribute List: 
Number of Attributes 
Not Supported 
Analog value (UINT16) 
not supported 
Vendor ID 
Services Supported: 
Get_Attribute_Single 
Analog Output Point – Class Code 
0x0B 
Attributes Supported: 
Class Instance Support (0x00) 
Class Attributes: 0x02 (Max Instance) 
Two instances supported (0x01 and 0x02) 
Attribute List: 
Number of Attributes 
not supported 
Analog value (UINT16) 
not supported 
Vendor ID 
Services Supported: 
Set_Attribute_Single; 
Get_Attribute_Single 
TCP/IP  Interface  Object  –  Class 
Code 0xF5 
Attributes Supported: 
One instance supported (0x01) 
Attribute List: 
Status 
Configuration Capability 
Configuration Control 
Physical Link Object 
Interface Configuration 
Host Name 
Services Supported: 
Get_Attribute_Single 
EtherNet  Link  Object  –  Class 
Code 0xF6 
Attributes Supported: 
One instance supported (0x01) 
Attribute List: 
Interface Speed 
Interface Flags 
Physical Address 
Interface Counters 
Media Counters 
Services Supported: 
Get_Attribute_Single 
Data  Table  Object  –  Private 
Object 
Attributes Supported: 
This object does not support instances or attributes 
but  uses  the  data  table  structure,  and  associated 
tags, in Logix5000 PLC’s. 
Services Supported: 
CIP Read Data