TROUblESHOOTING
Technical Support is available Monday through Friday, 7:00 a .m . to 5:00 p .m . CST, at (800) 334-6011 . Use the guide below to help find and correct 
system faults and then contact Technical support before replacing the unit or components or for additional troubleshooting . 
Table 4 – Troubleshooting Guide 
Symptom
possible Reason
Troubleshooting procedure
ERV will not turn on .
No power to blower .
• Check that the ERV is plugged in.
• Check that the power switch on the ERV is ON.
• If wired to an external control, verify wire connections inside ERV and at control.
• Connect the two yellow wires in the ERV. If the blower turns on, the problem
resides with the external control . Troubleshoot the control in accordance with 
the manufacturer’s instructions .
ERV blower is running, 
but little or no airflow .
Incorrect damper position .
• Verify that the dampers are not closed.
• Check for blocked duct work and clear.
12