Dry Contact I/O SmartSlot Card
Dip switches: input and outputs
The table below lists the four possible configurations, with their corresponding 
inputs and outputs.
* With this setup (the factory default), the Configuration Utility is used automatically.
Configuration 1
Configuration 2
Configuration 3
Configuration 4*
OFF-OFF-OFF-ON
ON-OFF-OFF-ON
OFF-ON-OFF-ON
ON-ON-OFF-ON
Inputs
Device Actions
1
Turn the UPS on.
See 
Configuration 
Utility
2
Turn the UPS off.
Turn the UPS off 
safely.
3
Start UPS self-test.
4
Shut down the UPS 
when on battery 
except for self-test or 
runtime calibration.
Put the UPS in 
bypass, if bypass is 
available on the 
UPS.
Shut down the UPS 
when on battery 
except for self-test or 
runtime calibration.
Outputs
Device State
1
The UPS is on-battery (e.g., during a power failure, self-test, or 
runtime calibration).
See 
Configuration 
Utility
2
The UPS has a low battery.
3
The protected load is not receiving power from the UPS or 
communication between the UPS and the Relay I/O Card has been 
lost.
4
Replace the UPS battery.
UPS commanded to 
turn on 
(echo of Input 1).
5
The UPS is 
overloaded.
The UPS is in bypass 
by selection from 
software, front panel, 
or rear panel.
UPS commanded to 
turn off gracefully 
(echo of Input 2).
6
Any UPS fault or 
self-test failure.
Any UPS fault, self-
test failure, or 
overload.
Any UPS fault, self-
test failure, overload, 
or replace battery