2.10  Master / Slave Wiring 
The interface wiring between the two operators requires four (4) 18 AWG wires for control. Each 
operator must be connected to it's own power source as described in section 2.2. Be sure that both 
operators are wired to the same phase in the breaker panel.  Check at the breaker panel by 
measuring voltage from HOT to HOT.  This should read 0 volts.  If the meter reads 230 Volts, change 
the wiring.  The loop functions are controlled by a two-channel loop detector (P/N 9405-010) plugged 
into the OPEN port on the operator that is designated as the master unit.  Color code shown assumes 
use of DoorKing master / slave cable, part number 2600-755 (30 ft.), 2600756 (40 ft.), 2600-757 (50 
ft.). 
 
1.  Connect the master / slave wiring main terminals 1, 4, 6 and external sensor terminal 2 
as shown below. Be sure that power to both operators is OFF. 
2.  Set SW 1, switch 3 to the OFF position in this operator.  Place a jumper from terminal 2 
to terminal 4. 
3.  Plug the 9405 loop detector into the OPEN loop port. Connect the leads from the EXIT 
loop to TB 1. Connect the leads from the REVERSE loop(s) to TB 2. Connect TB 3 
Normally Open (N.O.) to terminal 6. Connect TB 3 Common (C) to terminal 13. 
4.  Connect the radio receiver as shown. 
5.  Connect any other OPEN devices to terminals 4 and 13. Connect standard external 
REVERSING devices to terminals 6 and 13. See section 2.7.2 for secondary entrapment 
prevention device wiring for master / slave operators. 
 
 
 
OPEN PHOTO BEAM
CLOSE PHOTO BEAM
OPEN EDGE
CLOSE EDGE
COMMON
COMMON
1  24V COMMON
5  PARTIAL OPEN
3  24V RADIO PWR
2  OPEN / RADIO RELAY
4  OPEN
6  REVERSE / STOP
1  24V COMMON
5  PARTIAL OPEN
3  24V RADIO PWR
2  OPEN / RADIO RELAY
4  OPEN
6  REVERSE / STOP
OPEN PHOTO BEAM
CLOSE PHOTO BEAM
OPEN EDGE
CLOSE EDGE
COMMON
COMMON
Loop 1
Loop 2
COM
NC
NO
24V Com
Relay
Radio Pwr
EXIT
LOOP
REVERSE
LOOP
Yellow
Orange
Brown
Gray
Yellow
Brown
Orange
Gray
Master / Slave Conduit
MASTER
SLAVE
DoorKing model 9405 detector plugged into EXIT port on board.
1
1
2
2
Secondary device terminal used is dependent on the type of secondary device used.
3
Wire colors shown assume use of DoorKing master / slave interface cable.
3
4
4
Connect chassis ground to chassis ground.
4
Title:
Date:
Rev.
Dwg. No.
DOORKING, INC.,  INGLEWOOD, CA  90301
Master / Slave Interface
A
9/03
M9310-065-6
 
29