Geo Brick Drive User Manual
Motor Setup
198
AC Induction (Asynchronous) Motor Setup
– With Encoder
Before you start
This section assumes that the encoder has been wired and configured correctly in the Encoder
Feedback section. And that moving the motor/encoder shaft by hand shows encoder counts in the
position window.
Feedback section. And that moving the motor/encoder shaft by hand shows encoder counts in the
position window.
The AC Induction Motor Setup section is conceived for Motor#4, which is most commonly used
in Geo Brick Drive applications as a Spindle.
in Geo Brick Drive applications as a Spindle.
Parameters with Comments ending with -User Input require the user to enter information
pertaining to their system/hardware.
pertaining to their system/hardware.
Caution
Using an external shunt resistor is highly advised with spindle
applications due to the excessive energy transmitted back into the Geo
Brick Drive during decelerations.
applications due to the excessive energy transmitted back into the Geo
Brick Drive during decelerations.
For simplicity and better presentation of the parameters to be set up, we will consider the following
example: A 4-axis Geo Brick Drive 8/16A, powered with 208VAC three-phase is driving a 230VAC
spindle on channel 4:
example: A 4-axis Geo Brick Drive 8/16A, powered with 208VAC three-phase is driving a 230VAC
spindle on channel 4:
#define Mtr4Speed
1760
; Motor Rated Speed w/o field weakening [rpm] -User Input
#define LineFrequency
60
; Line frequency for rated speed [Hz]
-User Input
#define Mtr4NoLoadCur
6.8
; Rated current at no load [A] -User Input
#define Mtr4Voltage
230
; Motor rated voltage [VAC] -User Input
#define Mtr4TimeCst
0.75
; Motor time constant (optional) [sec]
-User Input
#define Mtr4Poles
4
; Motor number of poles -User Input
#define ACBusVoltage
208
; Three-phase 208 VAC Bus Voltage -User Input
Commutation Angle, Current Mask: Ixx72, Ixx84
I472=1365
; Motors #4 Commutation phase angle (Geo Brick Drive specific)
I484=$FFF000
; Motors #4 Current-Loop Feedback Mask Word (Geo Brick Drive specific)
PWM Scale Factor: Ixx66
If Motor Rated Voltage > Bus Voltage:
I466=1.10*I7000
; Motor #4 PWM Scale Factor. Set to 10% above PWM Count.
If Bus Voltage > Motor Rated Voltage:
A Geo Brick Drive connected to 3-Phase 230 VAC Bus, driving a 110 VAC Induction Motor. In this
case, Ixx66 serves as a voltage limit for the motor
I466=1.10*I7000*Mtr4Voltage/ACBusVoltage
; Motor #4 PWM Scale Factor
Current Feedback Address: Ixx82
I482=$07801E
; Motor 4 Current Feedback Address