D9412GV2/D7412GV2 | Operation and Installation Guide | Specifications 
 
 
72 
Bosch Security Systems, Inc. | 5/05 | F01U003641B 
 
Specifications 
Table 27: 
Specifications 
 
Primary: 
Terminals 1  
and 2 
16.5 VAC 40 VA class 2 plug-in transformer (D1640) 
Voltage Input 
(Power Supply) 
Secondary: 
Terminals 4  
and 5 
Sealed lead-acid rechargeable battery (12 VDC, 7 Ah or 12 VDC, 17.2 or 18 Ah). 
The control panel supports up to two 12 VDC, 7 Ah batteries using the D122 Dual 
Battery Harness or two D1218 (12 VDC, 17.2 or 18 Ah) batteries using a D122. 
Current 
Requirements 
Control Panel: Idle 200mA; Alarm 500 mA 
Refer to the Current Rating Chart for Standby Battery Calculations section in the D9412GV2/D7412GV2 Approved 
Applications Compliance Guide
 (P/N: F01U003639) for the current draw requirements of other system components. 
All external connections are power-limited except battery terminals. 
Continuous 
Power Outputs 
Terminals 3, 
24, and 32 
1.4 A maximum at 10.2 VDC to 13.9 VDC (continuous supply) total for all devices 
and outputs supplied at Terminals 3, 24, and 32 and at the accessory and 
programming connectors. 
Alarm Power 
Output 
Terminals 6 
and 7 
2.0 A maximum at 10.2 VDC to 13.9 VDC output. Output can be steady or one of 
three pulsed patterns depending on programming. Refer to Relays in the 
D9412GV2/D7412GV2 Program Entry Guide (P/N: F01U003636). 
Switched Aux 
Power 
Terminal 8 
1.4 A maximum at 10.2 VDC to 13.9 VDC output. Continuous output is interrupted 
by Sensor Reset or alarm verification depending on programming. Refer to Relays in 
the D9412GV2/D7412GV2 Program Entry Guide (P/N: F01U003636). 
Power 
Outputs* 
Fire and 
Fire/Burglary 
Systems 
To comply with UL 985 and 864 listing standards for fire alarm systems (effective March 1, 1989), the 
total combined continuous and alarm current draw for the system during alarm conditions must be 
limited to 1.4 A provided by the primary power supply (rectified AC). If current draw for the system 
exceeds 1.4 A, remove connected devices until the current draw falls below 1.4 A. Then, connect the 
removed devices to a D8132 Battery Charger Module or to an external power supply (refer to 
Figure 25 on page 55). 
Minimum 
Operating 
Voltage 
10.2 VDC 
SDI Bus 
SDI Bus A (+): 
SDI Bus B (-): 
9 VDC 4572 m (15000 ft) maximum 
9 VDC 4572 m (15000 ft) maximum 
Telephone 
Connections 
Connection: 
Two telco 
line
s: 
RJ31X or RJ38X jack can connect the control panels. 
Bosch Security Systems D928 Dual Phone Line Module required for two phone line service. 
Supervision supplied by the control panel. 
Discharge 
Cycle 
13.9 VDC 
13.8 VDC 
12.1 VDC 
10.2 VDC 
10.0 VDC 
Charging float level. 
Charging status LED on. 
Low Battery and AC Fail Reports if programmed. Low Battery LED on. 
Minimum operational voltage 
Battery load shed (processing functions continue if AC is present). 
Battery 
Discharge/ 
Recharge 
Schedule 
Recharge 
Cycle 
AC ON 
 
13.7 VDC 
13.9 VDC 
Load shed relay resets, battery charging begins, Battery Trouble and AC Restoral 
Reports sent. 
Battery Restoral Report sent, Low Battery LED off. 
Charging status LED off, battery float charged. 
Temperature: 
0°C to +50°C (+32°F to +122°F) 
Environmental 
Relative 
Humidity: 
Maximum 95% non-condensing 
Arming 
Stations 
D720 Command Center, D1255 Command Center, D1256 Fire Command Center; D1257 Fire Alarm Annunciator; 
D1260 Alpha V Command Center; Keyswitch 
Point 
Thresholds 
On-board Points 
1 to 8
 
Open 
Normal 
Short 
Greater than 3.7 VDC, but less than 5.0 VDC. 
Greater than 2.0 VDC, but less than 3.0 VDC. 
Greater than 0.0 VDC, but less than 1.3 VDC. 
Compatible 
Enclosures 
D8103 Universal Enclosure, D8109 Fire Enclosure, D8108A Attack Resistant Enclosure, BATB-40 Battery Box