2000 Series | Program Entry Guide | 11.0 
Point Codes 
EN | 37 
 
Bosch Security Systems | 7/05 | 35114F 
 
11.1  Digit 1, Point Type 
For Digit 1 selections 3, 4, 5, 6, 7, 8, 9, B, C: If an alarm occurs on these points within 2 minutes of a closing 
(exit time expired, Excursion/Exit included), the system sends a RECENT CLOSING message with the Alarm 
Report. 
For Digit 1 selections 6, 7, 8, 9, B, C: If these points are faulted at the end of exit delay, the system waits a 
period equal to entry delay before sending an Alarm Report. If the system is not turned off, it sends an EXIT 
ERROR message with the Alarm Report. 
Set Digit 1 to 0 (zero) for points used for RF keypads and arming devices: If you want to use an RF 
keypad or other arming device, you must assign each device to a point number in order to learn the device into 
the system. Set Digit 1 to 0 for RF keypad and arming device points.  
Table 5: Digit 1 Selections 
 
Display Selection 
Description 
Disabled 
Point does not respond to opens or shorts. Set Digit 1 to 0 if you are using 
this point number for an RF Keypad or arming device. 
Fire  
Short on sensor loop starts fire alarm response. 
Open on sensor loop causes trouble response. 
Fire points are not bypassable. Single Ring programming option does not 
apply to Fire points. 
Missing Fire points generate a trouble response when the system is on or 
off. 
Fire with Alarm 
Verification (use Fire 
with Alarm Verification 
for Point 1 only) 
Short on sensor loop starts verification process: 
1.
 
Control panel removes power to Point 1 for 4 seconds to reset smoke 
detectors. 
2.
 
Short on loop within 120 seconds of reset starts alarm response. If the 
point remains normal or open for the 120-second verification window 
no alarm response occurs.  
3.
 
Verification is not recommended for RF points. 
4.
 
Missing Fire points generate a trouble response when the system is on 
or off. 
5.
 
RF Tamper for Fire points generates a trouble response when the 
system is on or off. 
6.
 
Do not use Fire Alarm Verification points as Cross or Partner points. 
Refer to Section 11.3 Digit 3, Point Options.