When power restores to the points, the 60-sec 
confirmation window starts. If any detector, reset 
during the verification time, experiences another 
alarm during the confirmation window, an alarm 
occurs. If there is no activity during this period, no 
alarm occurs and the verification window ends. If a 
Verification point senses another alarm after the 
window ends, a new verification cycle begins. Refer 
to 
When an Alarm Verification point senses an alarm, 
the control panel automatically removes power to all 
Resettable points connected to the area’s Reset 
Sensors relay. The sensor reset removes power to 
the sensors for the amount of time programmed in 
Verify Time. When power is reapplied, a 60-sec 
confirmation window begins. If the detector is still in 
alarm and experiences another alarm during the 
confirmation window, or a different Resettable 
Verification point in the area senses an alarm, an 
alarm occurs.  
Table 24 for an example of Verify Time
 
To meet UL 864 requirements, set A# 
Verify Time
 to 60 sec. 
Example: Verify Time is set for 20 sec. The alarm 
verification cycle starts when the detector senses 
smoke or fire. No report occurs.  
 
 
When the detector senses smoke or fire, the area’s 
sensor reset relay interrupts power to points 
connected to it for the time in Verify Time. 
Table 24: Verify Time 
 
 
Restart Alarm 
Verification Cycle if 
an Alarm 
Verification point 
activates. 
Verification Point 
Activiation 
Verify Time/Reset 
Sensors
 
60 sec 
Confirmation
 
Power removed, 
ignore activity 
Generate alarm if 
additional activity 
received. 
*
 
20 Sec 
60 Sec 
 
Example: Total 
Cycle time 80 sec 
 
A# Duress Enable 
Default: 
No 
Selection:  Yes or No 
Yes 
Enable Duress alarm for this area. 
No 
Disable Duress alarm for this area. 
 
Refer to Duress Type in Section 2.8 Miscellaneous  
on page 35 for an explanation of duress. 
The passcode you normally use for 
duress is not valid in an area with A# 
Duress Enable
 set to No
 
If a passcode with the appropriate  
L# Disarm authority is used to duress 
disarm an area with A# Duress Enable 
set to No, NO AUTHORITY appears in 
the display. Also, if the keypad display 
is moved to an area with A# Duress 
Enable
 set to No using 
[COMMAND][5][0], a valid duress 
disarm passcode does not send a 
duress report. 
For SIA CP-01 Compliance: 
A# Duress Enable
 must be set to Yes