The connection to a Building Management System (BIS) is done via an OPC server and the 
Ethernet 100BaseTX interface. For a multiple-building network, you must check with the 
network adminstrator if
the network is designed for multiple-building connections (e.g. no technical interference 
by varying ground potentials)
the bus users are designed for the network
Address Setting and Configuration
1.
Assign a unique physical address to each Panel Controller and Remote Keypad by setting 
the rotary switches and write it down on the label (Step 1 and 2, Figure 7Page 9).
Make sure that the redundant panels do have identical addresses.
2.
For configuration, set the 6-pin DIP switch (Step 3Figure 7Page 9).
3.
Mark the setting on the provided label (Step 4).
Note the DIP switch and address settings for the stand-alone and redundant configuration 
(Figure 9, Page 10).
Technical Specifications
NOTICE! 
DIP 6 on the Panel Controller of the FPA-1200 is inoperable, as it cannot be operated as a 
redundant panel.
LCD display / touch screen
320 x 240 pixels / 127.5 mm x 170 mm active surface
Operating and display elements
22 keys, 1 key switch, 11 LEDs, 1 reboot button
Interfaces
CAN1, CAN2, ETH1, ETH2, USB, RS232
Signal inputs
IN1/IN2
Max. CAN cable length in networks
L
max
 = 1000 m, depending on configuration, cable type and topology
Input voltage
20 V DC to 30 V DC
Power supply PRS 0002 A
+5 V DC ±4.5 %  /  max. 500 mA
Max. current consumption
-
Standby: 135 mA at 24 V DC
-
During alarm: 225 mA at 24 V DC
Permissible operating temperature
-5 °C to +50 °C
Permissible storage temperature
-20 °C to +70 °C
Dimensions (H x W x D)
190 mm x 404 mm x 60 mm
Weight
Approx. 2 kg