INSTALLER/CONFIGURATION MENU 
With Heat or A/C selected, 
press and hold the Menu button for at least 5 seconds. The display will show item #1 in the 
table below. Press Menu to advance to the next menu item. Press 
 or 
 to change a menu item options. 
INSTALLER/CONFIGURATION MENU
Menu
Ref.
HP SS
Press
Button
Displayed 
(Factory Default)
Press 
 or 
 
to select from listed 
options
Comments
1
1
1
MENU
(MS 2)
HP 1, HP 2, SS 1
Selects Multi-Stage (MS 2 No Heat Pump), 
 
Heat Pump 1 (HP 1, 1 compressor), 
Heat Pump 2 (HP 2, 2 compressor or 2 speed 
compressor), or Single Stage (SS 1)
2
2
2
MENU
(GAS) for SS or MS
(ELE) for HP1, HP2
ELE or GAS
GAS setting: furnace controls the blower
ELE setting: thermostat controls the blower
3
3
3
MENU
(On) E
OFF
Selects Energy Management Recovery (EMR)
On or OFF.  
(Not available in non-programmable mode)
4
4
MENU
(ME) Cr Heat
SL, FA
Selects Adjustable Anticipation, cycle rate, Heat
(This item only appears when MS 2 or SS 1 is 
selected above)
5
4
MENU
(ME) Cr A/C     
SL, FA
Selects Adjustable Compressor Anticipation 
(Heat Pump) this item only appears when  
HP 1, HP 2 is selected above
6
5
5
MENU
(ME) Cr A/C
or
(FA) Cr Aux Heat
SL, FA
SL
Selects Adjustable Anticipation, cycle rate, cool 
(when MS 2 or SS 1 is selected above) or
Selects the cycle rate for Auxiliary stage (when 
HP 1 or HP 2 is selected above)
7
6
6
MENU
(OFF) CL
On
Selects Compressor Lockout Off or On
8
7
7
MENU  
Heat A/C Off 
or
Aux Heat A/C Off
Heat A/C Off,
Heat Off with Fan icon,
Heat Off without Fan icon
A/C Off
System Mode Configuration
9
8
8
MENU
(OFF) CO
On
Selects Compressor Optimization
10
9
9
MENU
 (On) dL
OFF
Selects Display Light On or OFF
11
10 10
MENU
0 HI
(current temperature)
1 HI, 2 HI, 3HI, 4 HI,
1 LO, 2 LO, 3 LO, 4 LO
Adjustable Ambient Temperature Display
12
11 11
MENU
°F
(current temperature)
°C
Selects Fahrenheit/Celsius Temperature Display
13
12 12
MENU
(0) P
7
Defaults to P (0) non-programmable
 P (7) is 7-day programming 
14
13 13
MENU
PS (2)
Day, Night
4
Morn, Day, Eve, Night
Selects Program periods per day: 
4 = Morn, Day, Eve, Night
2 = Day, Night
(Skipped if non-programmable)
15
14
MENU
(On) FA Heat
OFF
Fast Heat option may be disabled by
selecting OFF. NA to SS or HP1 config.
16
15 14
MENU
(On) FA A/C
OFF
Fast Cool option may be disabled by
selecting OFF. NA to SS or HP1 config.
17
16 15
MENU
(On) dS
Off
Selects Automatic Daylight Saving Time option
18
17 16
MENU
(99) HL Heat
62 to 98
Select's Limited HEAT Range
19
18 17
MENU
(45) LL A/C
46 to 82
Select's Limited A/C Range
20
19
MENU
 (0) dF
1 to 9
Selects dF (Dual Fuel) setting. 0 is Off
(If Dual Fuel option is required, a selection of 5 
is recommended)
MENU
(60) Cd
0 to 99
Selects compressor delay in seconds when dF 
is greater than 0
21
20 18
MENU
 (o) A/C On
Heat (b)
Selects operation of the reversing valve terminal 
(O/B) output as an O or B terminal
22
21 19
MENU
Returns to Normal Operation