6 - COMBUSTION AIR AND VENT PIPING  - CATEGORY I (CHIMNEY VENT)
6.1 Check Your Chimney
Chimney must be clean, right size, properly constructed
and in GOOD CONDITION.
1. 
Installation must conform to requirements of the 
authority having jurisdiction or, in absence of such 
requirements, to the National Fuel Gas Code, ANSI 
Z223.1/NFPA 54 and/or Natural Gas and Propane 
Installation Code, CAN/CSA B149.1.
2. 
Increaser fi tting is required on this boiler for Category I 
venting, and 4” is minimum permissible vent diameter. 
This does not imply vent connector is intended to be 4” 
diameter pipe. Vent connector shall be sized according 
to appropriate venting tables in the National Fuel 
Gas Code and may be required to be larger than 4” 
diameter. 
NOTICE
Boiler installation for chimney venting is not
complete unless increaser fi tting is located and
secured.
3. 
These are Category I and Category III high effi ciency 
boilers with lower stack or exhaust temperature.
4. 
Venting into masonry chimney without liner, line 
chimney from top to bottom with either:
A.  Listed Type B vent pipe
B. Listed fl exible vent liner
C.  Poured ceramic liner.
5. 
Outside chimneys should not be used unless they are 
(choose one of the following):
A.  Enclosed in a chase
B.  Lined with Type B vent pipe
C. Use listed fl exible vent liner
D. Use certifi ed chimney lining system
6. 
Vent connector from boiler to chimney should run as 
directly as possible with as few elbows as possible.
7. 
Common venting shall not be allowed. Boiler and 
other certifi ed appliances. appliances can share same 
chimney vent. Consult appropriate Vent Sizing Tables 
in National Fuel Gas Code for specifi c requirements of 
multiple appliance venting.
8. 
Boiler is only appliance connected to vent, Type B vent 
pipe is recommended for vent connector.
9. 
Slope pipe up from boiler to chimney not less than 1/4” 
per foot (21mm/m).
10. 
End of vent pipe must be fl ush with inside face of 
chimney fl ue. Use sealed-in thimble for chimney 
connection.
11. 
Fasten sections of vent pipe with sheet metal screws to 
make piping rigid. Use stovepipe wires to support pipe 
from above.
12. 
Do not connect to fi replace fl ue.
13. 
Do not install damper on this boiler.
 WARNING
Boiler and venting installations shall be performed 
by a qualifi ed service agent and in accordance with 
the appropriate manual. Installing or venting boiler 
or other gas appliance with improper methods or 
materials may result in serious injury or death due 
to fi re or to asphyxiation from poisonous gases such 
as carbon monoxide with is odorless and invisible.
!
     
 WARNING
Do not connect boiler to any portion of mechanical 
draft system operating under positive pressure.
!
     
Figure 11  - Combustion Air Fitting
Horizontal Venting requires fi eld supplied appliance adapter 
for the boiler fl ue outlet.  
Boiler is provided with a 3” vent connection, 3” x 4” 
increaser must be fi eld sourced for chimney application. 
This does not mean that the connection to the chimney will 
always be 4”.