Utica Boilers UB95M-200 快速安装指南

下载
页码 11
Select Parameter Definitions 
(see manual 240006105 for full list) See pages 6 & 7 for Factory Settings
DEFAULT LOWER
UPPER
PARAMETER
NAME
DESCRIPTION
VALUE
LIMIT
LIMIT
1
T3 Set
DHW target temperature (See Parameter 33)
150˚F
68˚F
158˚F
2
DHW System
01 = ON
DISPLAY-01
N/A
N/A
3
CH System
01 = ON
DISPLAY-01
N/A
N/A
4*
T1 Top
Maximum target supply water temperature
180˚F
68˚F
182˚F
5*
T1 Foot
Minimum target supply water temperature
120˚F
60˚F
140˚F
6*
T4 Minimum
Outside temp at which the target supply 
temperature is at maximum
0˚F
-4˚F
50˚F
7*
T4 Maximum
Outside temp at which the target supply 
temperature is at minimum
60˚F
60˚F
78˚F
33
T Plus
This value plus parameter 1 equals the
DHW set point.
30˚F
0˚F
54˚F
*Parameters 4-7 define the boilers Outdoor Reset Curve. See pages 6 & 7 for examples of the Outdoor Reset Curve.
5