INSTALLATION AND SETUP
The Economizer module may be mounted in any orientation. 
However, mounting in the orientation shown above permits 
proper viewing of the LCD display and use of the keypad.
NOTE: Jade will be in the "set up" mode for the first 60 
minutes after powered. If a sensor for OA air or 
Sylkbus device (sensor, actuator) is discon-
nected during the set up mode, the Jade will not 
alarm that failure. The MA sensor is a system 
"critical" sensor; if the MA sensor is removed 
during the set up mode, the Jade will alarm. After 
60 minutes the Jade controller will change to 
operation mode and all components removed or 
failed will alarm in the operation mode. 
WIRING
All wiring must comply with applicable electrical codes and 
ordinances, or as specified on installation wiring diagrams. 
Module wiring in the field is terminated to the four screw 
terminal blocks located on the left and right sides.
Module wiring at the OEM factory is terminated via the header 
pin terminals located on the left and right sides. The header 
terminal pins and the terminal blocks have common 
terminations for the appropriate input or output. The part 
number for the OEM female mating connector is 0039973997.
WARNING
Electrical Shock Hazard.
Can cause severe injury, death or property 
damage.
Disconnect power supply before beginning wiring, or 
making wiring connections, to prevent electrical shock 
or equipment damage.
CAUTION
Equipment Damage Hazard.
Electrostatic discharge can short equipment 
circuitry.
Ensure that you are properly grounded before 
handling the unit.
Each terminal can accommodate the following gauges of wire:
• Single wire – from 18 AWG to 22 AWG solid or stranded
• Multiple wires – up to two 22 AWG stranded
• For the 24 Vac connections: single wire – from 14 to 18 
AWG solid or stranded
For S-BUS wiring, the sensors may be mounted up to 200 ft. 
(61 m) from the JADE controller. When the length of wire is 
over 100 feet use twisted pair shielded wire.
NOTE: All wiring is polarity insensitive.
Refer to Fig. 1 through Fig. 6 for common wiring 
configurations.
Actuator Wiring Options:
1. The JADE economizer controller can only have one (1) 
communicating actuator connected to it.
2. Up to four (4) non-communicating and (2) 2-position 
actuators (1 each on EXH1 and AUX1 O)
3. One (1) communicating and up to four (4) non-commu-
nicating and (2) 2-position actuators (1 each on EXH1 
and AUX1 O)
When using a 2-position actuator on the AUX1 O the AUX1 O 
must be programmed for Exh2 and the % open is the % open 
of the outdoor damper when the 2-pos actuator opens. 
Connect 24 V to Exh1 and/or AUX1 O and ground to the Jade 
"C" terminal.