SERIES 2 – Q3452 Spark Pilot Retrofi t 
KIT# 550002585 
INSTALLATION INSTRUCTIONS
 WARNING
Fire, explosion, asphyxiation and electrical shock 
hazard.  Improper installation could result in death or 
serious injury.  Read this instruction and understand 
all requirements, including requirements of authority 
having jurisdiction, before beginning installation.  
Installation not complete until appliance operation 
is verifi ed per Installation, Operation & Maintenance 
Manual provided with boiler.
!
  
This kit is for both natural gas and LP versions.  Pilot is 
shipped for natural gas, a conversion package is included in 
this kit.
Following instructions for installation of Q3452 Spark Pilot 
Retrofi t Kit for Series 2 Boilers. 
1. 
Follow instructions to TURN OFF GAS TO APPLIANCE 
found on Operating Instructions label on boiler or in 
Installation, Operation & Maintenance Manual. Verify all 
electrical power to boiler is turned off.
 WARNING
Electrical shock hazard. Turn OFF electrical power 
supply at service panel.
!
  
2. 
Allow boiler to cool for 30 minutes before starting 
installation.
 WARNING
Burn hazard.  Verify heat exchanger and igniter 
have cooled or use appropriate personal protection 
equipment before removing pilot.
!
  
3. 
Remove front boiler door.
4. 
Disconnect spark cables from control board.
5. 
Disconnect pilot tube from gas valve. Loosen 
compression fi tting located on top of gas valve.
6. 
Locate current pilot assembly in front of base. See 
Figure 1.
7. 
Remove top burner door and burner tubes.              
8. 
Remove two pilot mounting screws holding pilot 
assembly in place. Remove entire pilot assembly. 
9. 
If this is LP Boiler, convert pilot to LP confi guration 
using enclosed pilot orifi ce.
10. 
This step is for 2 section boiler only. Remove pilot 
assembly from box.  Bend pilot tubing as shown in 
Figure 2 (tight 180º, then 90º back) in order to get it in 
between upper and lower burner doors.  
Kit# 550002585 Contents
Qty
Natural Gas spark/standing pilot assembly
Pilot Assembly Mounting Screws
2
Gas Valve Compression Fitting
1
LP Pilot Orifi ce
1
Burner 
Door
Pilot 
Mounting 
Screws
Burner 
Tubes
Lower 
Front 
Panel
Figure 1 - Base Front (3 Section Shown)
Figure 2 - Bend Pilot Tubing (Shield Not Shown for   
Clarity)