APOGEE Unit Vent Controller
0 to 10 V Output Owner’s Manual 
10  
 
Siemens Building Technologies. Inc. 
Application 2281 – Heating and/or Chilled Water 
Cooling, ASHRAE Cycles I and II 
In Application 2281, the Unit Vent Controller
⎯0 to 10V Output controls a unit ventilator 
equipped with a chilled water coil for cooling, and/or a heating coil, which may be hot water, 
steam, or electric, for ASHRAE Cycles I and II. A face-bypass damper can be controlled, 
replacing both the modulating (0-10V) heating and cooling actuators. If a face-bypass 
damper is used, the two-position valves on the coils can be controlled. Heating only and 
cooling only units can also be controlled with this application by overriding HEAT.COOL 
(Point 5).  
Other features available in this application include morning warm-up/cool down, night mode 
override, free cooling and auxiliary radiation in heating mode.  
NOTE: 
The use of a low temperature detection thermostat (LTDT) is strongly 
recommended for hot water and steam systems.  
This application controls room temperature by resetting the discharge air temperature. It also 
controls an outdoor air damper according to the schedules as defined by ASHRAE Cycles I 
and II. The free-cooling/economizer function is turned on and off by the field panel using 
FREE CLG (Point 23). If free cooling is not available, the outdoor air damper will be kept at 
minimum position; otherwise, the outdoor air damper will modulate open in sequence with the 
heating and cooling actuators. The unit ventilator fan is also controlled in this application.  
 
Figure 4.  Application 2281 Control Drawing.