Fume Hood Controller Owner's Manual 
 
Siemens Building Technologies, Inc. 
24V COMMON
24V HOT
GROUND
LAB00140R1
 
FLN TRUNK
+ -
S
(SHIELD)
(SHIELD)
(+)
(+)
(-)
(-)
TEC0470R1
 
Figure 2.  Power Wiring. 
Figure 3.  Communication Wiring. 
Controller LED Indicators 
The controller has six Light Emitting Diode (LED) indicators. See Table 2. 
Table 2.  Controller LEDs. 
LED Type 
Label  
(if present)* 
Indication 
DO 
LED 1 - LED 3 
Indicates the ON/OFF status of the DO associated with it. A 
glowing LED indicates that the DO is energized. 
Transmit 
TX 
Indicates, when flashing, that the controller is transmitting 
information to the field panel. 
Receive 
RX 
Indicates, when flashing, that the controller is receiving 
information from the field panel. 
BST 
”Basic Sanity Test” 
BST 
Indicates, when flashing ON and OFF once per second, that 
the controller is functioning properly. 
Operator Display Panel (ODP) 
The Operator Display Panel (ODP) is the interface device between the Fume Hood Controller 
and the operator. Its main functions are to display normal, warning, and alarm conditions to 
the operator. The ODP consists of a housing, three Light Emitting Diodes (LEDs), a liquid 
crystal display (LCD), four buttons, and a portable operator's terminal port. See Figure 4. The 
ODP buttons function as follows: 
Horn Silence button – Pressing the Horn Silence button turns the audible alarm off for the 
current alarm event. 
Emergency Purge button – Pressing the Emergency Purge button removes contaminated 
air from the fume hood by switching to an emergency exhaust flow level. The internal audible 
alarm will sound. Emergency Purge automatically overrides any other control mode in the 
Fume Hood Controller.