Fume Hood Controller Owner’s Manual 
18 
 
Siemens Building Technologies, Inc. 
Address Descriptor 
Description 
15 
EMER STPT 
A value of the preset FLOW STPT, in percent, that the controller uses as the 
setpoint when EMER ALM is ON. 
16 
LOW WARN 
This point displays an ON or OFF status. When the exhaust flow goes below the 
value specified at LOW WARN LMT for the time specified in ALARM TIME, the 
point goes into a warning state (ON); the yellow LED is illuminated at the ODP. 
17 
HIGH WARN 
This point displays an ON or OFF status. When the exhaust flow goes above the 
value specified at HI WARN LMT for the time specified in ALARM TIME, the 
point goes into a warning state (ON), the yellow LED is illuminated at the ODP. 
19 
ALM AKNLG 
This point displays an ON or OFF status that indicates the Horn Silence button 
has been pressed at the ODP to acknowledge an alarm condition. The point will 
reset when the alarm condition clears or another alarm is initiated. 
27 
AO2 DEADBAND 
When EXH FLOW and FLOW STPT are different by more than the AO2 
DEADBAND, the AO2 FLOW SIG changes from setpoint to actual flow. 
30 
AO2 RANGE 
Scaling for the Analog Output (AO2) point. To get the correct output, the slope 
and intercept of this point must match the point database of the room controller. 
34 
TRANS RANGE 
The maximum range, in inches of water (PA), of the differential pressure 
transmitter. Standard values are 0.1 (25.3), 0.25 (62.275), 0.5 (124.55), and 1.0 
(253). 
35 
EXH FLOW 
The calculated value, in CFM (LPS), of the exhaust airflow as measured with the 
differential pressure transmitter sensor. 
36 
FLOW COEFF 
Gain factor for the flow sensor. 
37 
FLOW STPT 
Setpoint, in CFM (LPS), that the airflow is controlled to. 
38 
FLOW LO STPT 
The low flow setpoint used in FLOW STPT. 
40 
CAL DP TRANS 
YES or NO point used to calibrate the zero point of the differential pressure 
transmitter. 
41 
DO1 SUP 
Digital output 1 is used to control the analog output-pneumatic (AO-P) supply 
valve or the AO-E module supply input. 
42 
DO2 EXH 
Digital output 2 is used to control the analog output-pneumatic (AO-P) exhaust 
valve or the AO-E module exhaust input. 
43 DO3 
Digital 
output 
3 is a spare output. 
44 
AI1 DP TRANS 
Analog input 1, a 4 to 20 mA signal from the differential pressure transmitter. 
The point displays the mA value of input from the sensor. 
45 
AI2 0.10V 
Analog input 2 is a 0 to 10 Vdc spare input. 
46 
AO1 0.10V 
Spare analog output is a 0 to 10 Vdc output. 
47 
AO2 FLOW SIG
 
Analog output 2 signal is used to indicate the exhaust flow setpoint. The output 
is 1 to 10 Vdc, which corresponds to 0 to A02 RANGE (Point 30). 
48 
DI1 STPT SW 
Digital input for dry contact connection to control the HI/LOW flow setpoint of the 
controller. 
54 
ODP DISPLAY 
Controls the function of the  ODP display.  It will display either CFM divided by 
10 or HI FLOW / LO FLOW. 
55 
DO3 MODE 
Controls the function of the DO3.  It will follow either the HI/LO setpoint or the 
alarm status.